Q9 Plus ASD Installation and Operation Manual
213
Communications Option Speed Switch Monitor DeviceNet/
CC-Link
Program
Communications
Communication Options
This parameter is used in the setup of the communications network by reading
the hardware-specific settings of the option card being used with the ASD.
If using the
DEV002Z
Devicenet card, this parameter reads the hardware
switch SW300 setting of the Devicenet card. SW300 sets the baud rate and the
MAC address of the option card that is connected to a node of the
communications system.
See the
DeviceNet Option Instruction Manual
(P/N 58683) for additional
information on this parameter or see the instruction manual for the option being
used with the
Q9 Plus ASD
.
Direct Access Number — F854
Parameter Type —
Hardware Selectable
Factory Default
—
0
Changeable During Run
—
Yes
Minimum — 0
Maximum
— 255
Free Notes
Program
Communications
Communication Settings
This is an unused parameter that has allocated memory space.
The space may be used at the discretion of the user. This space may be used to
store information or a note to be transferred using communications.
Direct Access Number — F880
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 65535
Network Option Reset Setting
Program
Communications
Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the targets of a Reset command received via the communications
link.
Settings:
0 — ---
1 — Reset Option Board and ASD
Direct Access Number — F899
Parameter Type —
Selection List
Factory Default —
- - -
Changeable During Run —
No
Input Function Target 1
Program
My Function
My Function Unit 1
This parameter plays a role in the setup of the
My Function
feature by
selecting the functionality of the programmable
Input Function Target 1
terminal.
This setting assigns the function of the programmable
Input Function Target 1
terminal to any one of the user-selectable functions listed in
Table 12 on pg.
238
,
Table 13 on pg. 239
, or
Table 15 on pg. 242
.
See
F977
for additional information on this parameter.
Direct Access Number — F900
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
No
Input Function Command 1
Program
My Function
My Function Unit 1
This parameter is used to assign a user-selected logical operator to two user-
selected
Input Function Target
variables, enable a counter/timer function, or
perform a hold/reset function.
Table 16 on pg. 244
lists the available selections. Their use and selection
requirements are described in an example at
F977
.
Direct Access Number — F901
Parameter Type —
Selection List
Factory Default —
0 (NOP)
F854
F901