Q9 Plus ASD Installation and Operation Manual
217
Input Function Target 3
Program
My Function
My Function Unit 3
This parameter plays a role in the setup of the
My Function
feature by
selecting the functionality of the programmable
Input Function Target 3
terminal.
This setting assigns the function of the programmable
Input Function Target 3
terminal to any one of the user-selectable functions listed in
Table 12 on pg.
238
,
Table 13 on pg. 239
, or
Table 15 on pg. 242
.
See
F977
for additional information on this parameter.
Direct Access Number — F916
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
No
Output Function Assigned
Program
My Function
My Function Unit 3
This parameter plays a role in the setup of the
My Function
feature by
selecting the functionality of the
Output Function Assigned
terminal.
This setting assigns the function of the programmable
Output Function
Assigned
data location to one of the functions listed in the
Input Setting
field
of
Table 13 on pg. 239
.
Settings:
0 – 3099
See the
My Function Instruction Manual
(P/N E6581335) and
F977
for
additional information on this parameter.
Direct Access Number — F917
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
No
My Function Percent Data 1
Program
My Function
My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the
My Function Percent Data 1
.
The analog signal is selected using the
Input Setting
number from
Table 13 on
pg. 239
.
Once the assigned output value reaches the threshold setting of this parameter
the output value is transferred to
My Function Out 1
.
See the
My Function Instruction Manual
(P/N E6581335) and
F977
for
additional information on this parameter.
Direct Access Number — F918
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Percent Data 2
Program
My Function
My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the
My Function Percent Data 2
.
The analog signal is selected using the
Input Setting
number from
Table 13 on
pg. 239
.
Direct Access Number — F919
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.00
Units — %