Q9 Plus ASD Installation and Operation Manual
227
Analog Input Function Target 21
Program
My Function
My Function Analog
This parameter plays a role in the setup of the
My Function
feature by
selecting the functionality of the programmable
Analog Input Function
Target 21
terminal.
The function selected at
F964
may be adjusted using the input analog control
signal selected here.
Settings:
0 — Disabled (None)
1 — V/I
2 — RR
3 — RX
4 — Optional RX2+, RX2-
5 — Optional V/I
6 — Internal Memory
Direct Access Number — F962
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
Yes
Analog Function Assigned Object 21
Program
My Function
My Function Analog
This parameter plays a role in the setup of the
My Function
feature by
selecting the functionality to which the adjustment of
F962
is applied.
Settings:
0 — Disabled (None)
1 — Acceleration Rate
2 — Upper-Limit Frequency
3 — Acceleration Multiplication Factor
4 — Deceleration Multiplication Factor
5 — Manual Torque Boost
6 — Over-Current Stall (
F601
)
7 — Thermal Protection
8 — Speed Loop Proportional Gain (
F460
)
9 — Drooping Gain (
F320
)
10 — PID Proportional Gain (
F362
)
See the
My Function Instruction Manual
(P/N E6581335) for a complete
description of the setup requirements and operational information of the
Analog Function Assigned Object
parameter.
Direct Access Number — F964
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
No
Monitor Output Function 11
Program
My Function
My Function Monitor
This parameter plays a role in the setup of the
My Function
feature by
establishing the function that is to be recorded and output as the
Peak
,
Minimum
, or
Average
value as selected at parameter
F966
.
Select the
Monitor Display Input Setting
number from
Table 15 on pg. 242
to
output the corresponding function.
Use the Communication Number if operating using communications.
See the
My Function Instruction Manual
(P/N E6581335) for a complete
description of the setup requirements and operational information of the
Monitor Output Function
parameter.
Direct Access Number — F965
Parameter Type —
Selection List
Factory Default —
2000
Changeable During Run —
Yes
F962
F965
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com