background image

Q9 Plus ASD Installation and Operation Manual

15

Connecting the ASD

Refer to the section titled 

Installation Precautions on pg. 4

 and the section titled 

Lead Length 

Specifications on pg. 19

 before connecting the ASD and the motor to electrical power.

Power Connections

C o n t a c t   W i t h   3 - P h a s e   I n p u t / O u t p u t   T e r m i n a l s   M a y   C a u s e  

E l e c t r i c a l   S h o c k   R e s u l t i n g   I n   I n j u r y   O r   L o s s   O f   L i f e .

See 

Figure 20 on pg. 25

 for a system I/O connectivity schematic.

An inductor (DCL) may be connected across the 

PO

 and 

PA/+ 

terminals to provide additional filtering. 

When not used, a jumper must be connected across these terminals (see 

Figure 20 on pg. 25

).

PA/+

 and 

PB

 are used for the DBR connection. The DBR function is NOT used on the 

Q9 Plus ASD

.

PC/-

 is the negative terminal of the DC bus.

R/L1

,

 S/L2

, and

 T/L3

 are the 3-phase input supply terminals for the ASD.

U/T1

V

/

T2

, and 

W/T3

 are the output terminals of the ASD that connect to the motor.

The location of the 

Charge Indicator LED

 for the smaller typeform ASD is provided in 

Figure 2

. The 

Charge Indicator LED

 is located on the front door of the enclosure of the larger ASDs.

Figure 2. Typical Q9 Plus ASD input/output terminals and the 

Grounding Capacitor Switch

.

DANGER

DANGER

Grounding Capacitor Switch

 — Pull for 

Small

 capacitance/push for 

Large

 capacitance.

Note:

PO-to-PA/+ shorting bar removed to show reference designators.

Charge 
Indicator
LED

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Summary of Contents for VLP Technology Q9 Plus

Page 1: ...TM Q9 Plus ASD Install Op Manual TOSHIBA Q9 Plus ASD INSTALLATION OPERATION MANUAL DN 68249 000 February 2013 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 2: ...Document Number 68249 000 February 2013 Q9 Plus ASD Installation Operation Manual TM Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 3: ...ad machine wear pattern for all motors and pumps of the system by optimizing load sharing such that all pumps are allowed to alternate as the primary pump while the remaining pump s operate in an ancillary mode for time intervals that are determined by the user Time Based Alternation also offers a significantly decreased level of system down time during a pump failure by allowing the system to ope...

Page 4: ...act between the parties is the sole warranty of Toshiba International Corporation and any statements contained herein do not create new warranties or modify the existing warranty Any electrical or mechanical modifications to this equipment without the prior written consent of Toshiba International Corporation may void all warranties and may void the UL CSA listing or other safety certifications Un...

Page 5: ...ed throughout the manual Read the manual completely before installing operating performing maintenance or disposing of this equipment This manual and the accompanying drawings should be considered a permanent part of the equipment and should be readily available for reference and review Dimensions shown in the manual are in metric and or the English equivalent Because of our commitment to continuo...

Page 6: ...sit our web site TOSHIBA INTERNATIONAL CORPORATION Q9 Plus Adjustable Speed Drive Please complete the Warranty Card supplied with the ASD and return it to Toshiba International Corporation by prepaid mail This will activate the 12 month warranty from the date of installation but shall not exceed 18 months from the shipping date Complete the following information and retain for your records Model N...

Page 7: ...ions 7 Personnel Protection 7 System Setup Requirements 8 Dynamic Braking Precaution 8 Operational and Maintenance Precautions 9 Motor Characteristics 10 Motor Autotuning 10 Pulse Width Modulation Operation 10 Low Speed Operation 10 Overload Protection Adjustment 10 Operation Above 60 Hz 10 Power Factor Correction 11 Light Load Conditions 11 Motor Load Combinations 11 Motor Braking 11 Q9 Plus ASD ...

Page 8: ...ng Changes 35 Command Mode and Frequency Mode Control 36 Command Control F003 36 Frequency Control F004 37 Command and Frequency Control Selections 37 Override Operation 37 Command and Frequency Control Override Hierarchy 38 Command Control Selections 39 Frequency Control Selections 39 System Configuration and Menu Options 41 Root Menu Items 41 Frequency Command Mode 41 EOI Command Mode 42 Monitor...

Page 9: ...s 251 Viewing Trip Information 256 Clearing a Trip 256 Part Numbering Convention and Enclosure Dimensions 257 Part Numbering Convention 257 Enclosure Dimensions 258 Voltage Current Specifications 264 Cable Terminal Specifications 266 Short Circuit Protection Recommendations 268 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 10: ... alert symbol indicates that an imminently hazardous situation exists that if not avoided or if instructions are not followed precisely will result in serious injury to personnel or loss of life The word WARNING preceded by the safety alert symbol indicates that a potentially hazardous situation exists that if not avoided or if instructions are not followed precisely could result in serious injury...

Page 11: ...icate an imminently hazardous situation that may result in serious injury severe property and equipment damage or loss of life if safe procedures or methods are not followed as outlined in this manual Qualified Personnel Installation operation and maintenance shall be performed by Qualified Personnel Only A Qualified Person is one that has the skills and knowledge relating to the construction inst...

Page 12: ...spections may be required after moving equipment Contact the TIC Customer Support Center to report discrepancies or for assistance if required Handling and Storage Use proper lifting techniques when moving the ASD including properly sizing up the load getting assistance and using a forklift if required Store in a well ventilated location and preferably in the original carton if the equipment will ...

Page 13: ... fluids Avoid installation in areas where vibration heat humidity dust fibers metal particles explosive corrosive mists or gases or sources of electrical noise are present The installation location shall not be exposed to direct sunlight Allow proper clearance spaces for installation DO NOT obstruct the ventilation openings Refer to the section titled Installation and Connections on pg 13 for furt...

Page 14: ...citor Switch The ASD is equipped with leak reduction capacitors which are used to reduce the EMI leakage via the 3 phase power input circuit and for compliance with the Electromagnetic Compatibility Directive EMC The effective value of the capacitor may be increased reduced or removed entirely via the Selector Switch Switching Bar or the Switching Screw the type used is typeform specific The Groun...

Page 15: ...fer to NEC Article 310 adjustment factors DO NOT connect the 3 phase input power to the output of the ASD This will damage the ASD and may cause injury to personnel DO NOT connect resistors across terminals PA PC or PO PC This may cause a fire Ensure the correct phase sequence and the desired direction of motor rotation in the Bypass mode if applicable Protection Ensure that primary protection exi...

Page 16: ...plication specific system integration information if required Personnel Protection Installation operation and maintenance shall be performed by Qualified Personnel Only A thorough understanding of the ASD will be required before the installation operation or maintenance of the ASD Rotating machinery and live conductors can be hazardous and shall not come into contact with personnel Personnel shoul...

Page 17: ...hly recommended i e E Off Overload Protection etc If a secondary magnetic contactor MC or an ASD output disconnect is used between the ASD and the load it should be interlocked to halt the ASD before the secondary contact opens If the output contactor is used for bypass operation it must be interlocked such that commercial power is never applied to the ASD output terminals U V or W When using an A...

Page 18: ...LED shown for smaller ASDs in Figure 2 on pg 15 LED is located on the front panel of larger ASDs Wait at least the minimum time indicated on the enclosure mounted label and ensure that the Charge Indicator LED has turned off once the ASD power has been turned off before coming into contact with any circuits DO NOT attempt to disassemble modify or repair the ASD Contact the TIC Customer Support Cen...

Page 19: ...by an ASD than when operated directly from commercial power Low Speed Operation Operating a general purpose motor at lower speeds may cause a decrease in the cooling ability of the motor Reducing the torque requirement of the motor at lower speeds will decrease the generated heat at lower speeds When the motor is to be operated at low speed less than 50 of full speed and at the rated torque contin...

Page 20: ... Load Combinations When the ASD is used in combination with one of the following motors or loads it may result in unstable operation A motor with a rated capacity that exceeds the motor capacity recommended for the ASD An explosion proof motor When using the ASD with an explosion proof motor or other special motor types lower the carrier frequency to stabilize the operation DO NOT set the carrier ...

Page 21: ... input voltage to a Q9 Plus ASD that is beyond that which the Q9 Plus ASD is rated The input voltage may be stepped down when required with the use of a step down transformer or some other type of voltage reduction system Using Vector Control Using Vector Control enables the system to produce very high torque over the entire operating range even at extremely low speeds Vector Control may be used w...

Page 22: ...ore the output contactor is opened DO NOT open and then close a secondary magnetic contactor between the ASD and the motor unless the ASD is off and the motor is not rotating Note Re application of power via a secondary contact while the Q9 Plus ASD is on or while the motor is still turning may cause ASD damage The Q9 Plus ASD input voltage should remain within 10 of the specified input voltage ra...

Page 23: ...e is adequate ventilation DO NOT operate the ASD with the enclosure door open The ambient operating temperature rating of the Q9 Plus ASD is 14 to 104 F 10 to 40 C When installing multiple ASDs horizontally Toshiba recommends at least 5 cm of space between adjacent units However horizontally mounted ASDs may be installed side by side with no space in between the adjacent units if the top cover is ...

Page 24: ...s these terminals see Figure 20 on pg 25 PA and PB are used for the DBR connection The DBR function is NOT used on the Q9 Plus ASD PC is the negative terminal of the DC bus R L1 S L2 and T L3 are the 3 phase input supply terminals for the ASD U T1 V T2 and W T3 are the output terminals of the ASD that connect to the motor The location of the Charge Indicator LED for the smaller typeform ASD is pro...

Page 25: ...onduit refer to NEC Article 310 adjustment factors Note National and local codes should be referenced when running more than three conductors in the same conduit Install a molded case circuit breaker MCCB or fuse between the 3 phase power source and the ASD in accordance with the fault current setting of the ASD and NEC Article 430 The ASD is designed and tested to comply with UL Standard 508C Mod...

Page 26: ...ecurely connected to ground Connect a surge suppressor to every electromagnetic contactor and every relay installed near the ASD Install noise filters as required Grounding Capacitor The Grounding Capacitor plays a role in minimizing the effects of leakage current through the ASD system and through ground paths to other systems Leakage current may cause the improper operation of earth leakage curr...

Page 27: ...y be set to Large default setting or Small by pushing or pulling the switch actuator respectively Figure 6 The Grounding Capacitor Bar is used on typeforms 200 volt 75 HP and the 100 HP 460 volt 125 HP and the 150 HP The value may be set to Large or Small default setting by connecting or disconnecting the switching bar respectively Figure 7 The Grounding Capacitor Screw is used on typeforms 460 vo...

Page 28: ... of the ASD Note Contact the TIC Customer Support Center for application assistance when using lead lengths in excess of those listed Exceeding the peak voltage rating or the allowable thermal rise time of the motor insulation will reduce the life expectancy of the motor When operating in the Vector Control mode the carrier frequency should be set to 2 2 kHz or above Table 1 Lead Length Recommenda...

Page 29: ...te output Figure 16 on pg 24 O2A B OUT2 Reach Frequency Multifunctional programmable discrete output FLA Fault relay N O Figure 19 on pg 24 FLB Fault relay N C FLC Fault relay Common RR Analog Input Frequency Mode 1 Multifunctional programmable analog input 0 0 to 10 volt input 0 Hz to Maximum Frequency Figure 11 on pg 24 RX Unassigned Multifunctional programmable analog input 10 to 10 VDC input U...

Page 30: ...g 234 see F112 S1 The default setting for this terminal is Fire Speed The function of this input as Fire Speed is to run the motor at the Preset Speed 1 setting upon activation This terminal may be activated by connecting CC to this terminal Sink mode and may be initiated by a fire alarm signal or fire smoke sensing device This input terminal may be programmed to any of the functions listed in Tab...

Page 31: ...to another ASD while retaining the control programming See the section titled Battery Backup on pg 27 for more information on the battery backup features P24 24 VDC at 200 mA power supply for customer use This terminal references CCA PP The function of output PP is to provide a 10 VDC 10 mADC output that may be divided using a potentiometer The tapped voltage is applied to the RR input to provide ...

Page 32: ...ontacts are rated at 2A 120 VAC and 2A 30 VDC Figure 8 FLA FLB and FLC Switching Contacts Shown in the Normal Operating Condition Figure 9 Terminal Board Sink Source TB1 TB2 TB3 TB4 See the section titled Terminal Descriptions on pg 21 for terminal descriptions See the section titled Cable Terminal Specifications on pg 266 for information on the proper cable terminal sizes and torque specification...

Page 33: ...ete Input Figure 11 RR Input Figure 12 RX Input Figure 13 V I Input Figure 14 P24 Output Figure 15 PP Output Figure 16 OUT1 OUT2 Output Figure 17 FP Output Figure 18 AM FM Output Figure 19 Fault Relay shown not faulted Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 34: ... analog terminals are referenced to CC The RR RX P24 and the PP analog terminals are referenced to CCA The isolated V I analog terminal references IICC Note When connecting multiple wires to any of ASD terminals do not connect a solid wire and a stranded wire to the same terminal Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 35: ... T L3 are connected to the 3 phase input power U T1 V T2 and W T3 are connected to the motor The 3 phase input voltage is within the specified tolerance There are no shorts and all grounds are secure All personnel are at a safe distance away from the motor and or the motor driven equipment DANGER Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 36: ...equipped with a battery backup system The function of the backup system is to retain the EOI SRAM programming in the event of a power outage or if an EOI removal and installation from one system to another is required without the loss of programming Listed below are the items retained by the battery backup system Trip History EOI Contrast Real Time Clock Information Monitored items Password and Lo...

Page 37: ...menu selection Press the Rotary Encoder to perform the Enter select function Hand Auto Key Toggles the system to and from the Hand and Auto modes The LED is on when the system is in the Hand Command mode The Hand mode allows the Command and Frequency control functions to be carried out via the EOI The Auto mode enables the Command and Frequency control functions to be carried out via the Terminal ...

Page 38: ...een displays the output frequency active alarms and or active faults If there are no active alarms or faults the output frequency is displayed During an active alarm the display toggles to and from the running frequency and the active alarm During an active fault the fault is displayed Loss of the ST to CC connection flashes Off LED Character Font Information Characters displayed on the LED screen...

Page 39: ...time the ESC key is pressed until the Frequency Command screen is reached Further ESC entries will toggle the system to and from the Frequency Command screen and the EOI Command menu Note Changes carried out from the EOI Command screen will be effective for EOI controlled ASD operation only See the section titled EOI Command Mode on pg 42 for further information on EOI Command Mode operations Prim...

Page 40: ...ng the Mounting Kit Note See Figure 25 for the dimensions and the item locations referenced in steps 1 7 1 At the EOI mounting location mark the 4 60 by 4 50 hole and the four 11 32 screw holes 2 Cut the 4 60 by 4 50 rectangular mounting hole 3 Drill the four 11 32 screw holes for the Bezel Plate mount 4 Attach and secure the Bezel Plate to the front side of the mounting location using the four 10...

Page 41: ...allation and Operation Manual Figure 25 Remote Mounting Dimensions inches millimeters Figure 26 Front Panel Removal Front Panel Connector Assembly Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 42: ...e the upper retaining tabs of the EOI panel Then pivot the EOI assembly away from the ASD and lift see Figure 26 5 Remove the EOI from the Front Panel Assembly of step 4 discard the assembly 6 Attach and secure the EOI to the front side of the mounting location using the four 6 32 x 5 16 pan head screws the 6 split lock washers and the 6 flat washers 7 Install the Front Panel Connector Assembly to...

Page 43: ...artups will resume The Startup Wizard querys the user for the following information 1 The Voltage and Frequency Rating of the Motor 2 The Upper Limit Frequency 3 The Lower Limit Frequency 4 Automatic Acceleration Deceleration if Enabled continue from step 7 5 The Acceleration Time 6 The Deceleration Time 7 The Volts Per Hertz Control Type 8 The Motor Current Rating 9 The Motor Rated Speed 10 The C...

Page 44: ...rameter Number of the setting to be changed at the Direct Access menu Program Direct Access applicable parameter number A listing of the Direct Access Parameter Numbers and a description of the associated parameter may be found in the section titled Direct Access Parameter Information on pg 82 Search For Default Setting Changes A listing of all parameters that have been changed from the factory de...

Page 45: ...ources managed by the Override function The level of the control item on the hierarchy is listed from left to right most to least respectively As indicated in the table the Override setting may supersede the F003 setting Placing the EOI in the Hand mode selects the RS485 2 Wire as the Command Mode control source Hand mode operation may be superseded by other Override settings Example With the EOI ...

Page 46: ...Hand mode places only the RS485 2 wire in the Override Mode Possible Frequency control source selections include the following Communication Card RS485 2 Wire RS485 4 Wire Panel Keypad Option Terminal Block default setting or F004 setting used if no other items are in the override mode Note The Terminal Board is placed in the Override Mode for Speed control functions by assigning a discrete termin...

Page 47: ...d Frequency control Override operation The Q9 Plus ASD reads the command registers of the listed control items from the left to the right The first item to be read that has the Override feature turned on will be used for Command or Frequency control Table 3 Command and Frequency Control Hierarchy Forced F003 F004 by I P Terminal Assign to Serial Local Switch Communication Card RS485 4 Wire RS485 2...

Page 48: ...n Board for command control Frequency Control Selections The following is a listing with descriptions of the Frequency Mode F004 selections Program Fundamental Standard Mode Selection Frequency Mode 1 Settings 1 V I Used when a 0 to 10 VDC analog input or a 4 20 mA or 0 to 1 mA DC current input is used as the speed control input Only one input signal type may be used at a time Set SW301 to the des...

Page 49: ...erface 10 UP DOWN Frequency A discrete terminal may be configured to increase or decrease the speed of the motor by momentarily connecting the assigned terminal to CC See F264 on pg 129 for further information on this feature 11 Optional RP Pulse Input Used to allow the system to use a pulsed input for frequency control 12 Optional High Speed Pulse Input Used to allow the system to use a pulsed in...

Page 50: ...requency Command screen when active Fault information will be displayed via a Fault screen See Alarms Trips and Troubleshooting on pg 245 for more information Figure 28 Q9 Plus ASD Root Menu Navigation Frequency Command Mode Frequency Setting While operating in the Hand mode Hand LED is illuminated the running frequency of the motor may be set from the Frequency Command screen Using the Rotary Enc...

Page 51: ...es may be selected and run Each V f profile is comprised of four user settings Base Frequency Base Frequency Voltage Manual Torque Boost and Electronic Thermal Protection Expanded descriptions of these parameters may be found in the section titled Direct Access Parameter Information on pg 82 Accel Decel Group One of two Accel Decel profiles may be selected and run Each of the Accel Decel profiles ...

Page 52: ...D AM Output Displays the magnitude of the function assigned to this terminal relative to the full scale reading of the AM terminal This terminal may be configured at F670 for application specific suitability FM Output Displays the magnitude of the function assigned to this terminal relative to the full scale reading of the FM terminal This terminal may be configured at F005 for application specifi...

Page 53: ...ange of the V I value Note The isolated V I input terminal may receive Current or Voltage to control the output speed or the output torque The input signal type must be selected at SW301 on the Terminal Board The V input setting of SW301 is used for the 0 10 VDC analog input signal and the I input setting of SW301 is used for the 0 20 mA analog input signal Either may be used as a frequency or tor...

Page 54: ...es Type Reset Reset to Factory Settings before pursuing a systemic malfunction Direction Displays the Direction command forward reverse Discrete Input Terminals Displays the status activated reverse video of the discrete input terminals of the Terminal Board Discrete Output Terminals Displays the status activated reverse video of the discrete output lines of the Terminal Board Output Frequency Dis...

Page 55: ...ion Time 1 F009 Deceleration Time 1 F010 Lower Limit Frequency F013 Current Voltage Display Units F701 Motor Overload Protection Level 1 F600 Output Terminal 1 OUT1 Function F130 PWM Carrier Frequency F300 Auto Restart F301 Number of Times to Retry F303 VIRTUAL LINEAR PUMP see Virtual Linear Pump Setup on pg 72 for more on this function Setup Wizard Motor Rated Current Nameplate F406 Application T...

Page 56: ...erminal 5 S1 Function F115 Sleep Timer Sleep Timer F382 Sleep Delay Timer F383 Run External Devices External Device Delay Timer F480 External Device Low Band Threshold F481 External Device High Band Threshold F482 Output Terminal 1 OUT1 Function F130 Output Terminal 2 OUT2 Function F131 Low Suction No Flow Cut Off Low Suction No Flow Cut Off Mode F483 Low Suction No Flow Cut Off Delay Timer F484 I...

Page 57: ...aximum Frequency F011 Upper Limit Frequency F012 Lower Limit Frequency F013 V f Pattern F015 Time Limit for Lower Limit Frequency Operation F256 Motor Set 1 Automatic Torque Boost F001 Base Frequency 1 F014 Manual Torque Boost 1 F016 Motor Overload Protection Level 1 F600 Standard Mode Selection Command Mode F003 Frequency Mode 1 F004 Forward Reverse Run F008 Frequency Priority Selection F200 Freq...

Page 58: ...Output Gradient Characteristic F692 MON 2 Bias Adjustment F693 MON 2 Voltage Current Output Switching F691 Pulse Output Function Not Used with the Q9 ASD F676 Pulse Output Frequency F677 Input Special Functions Forward Reverse Run Priority When Both Are Closed Activated F105 Input Terminal Priority F106 16 Bit Binary BCD Input F107 V I Analog Input Broken Wire Detection Level F633 Select Operation...

Page 59: ...nput Terminal 13 LI5 Function F123 Input Terminal 14 LI6 Function F124 Input Terminal 15 LI7 Function F125 Input Terminal 16 LI8 Function F126 Virtual Input Terminal Selection 1 F973 Virtual Input Terminal Selection 2 F974 Virtual Input Terminal Selection 3 F975 Virtual Input Terminal Selection 4 F976 Line Power Switching Commercial Power ASD Switching Output F354 Commercial Power ASD Switching Fr...

Page 60: ...TIES Utilities Version EOI ASD Type CPU Level EEPROM MC Level N A Display Parameters Automatic Function Selection F040 Current Voltage Display Units F701 Free Unit Multiplication Factor F702 Free Unit F703 Free Unit Display Gradient Characteristic F705 Free Unit Display Bias F706 Change Step Selection 1 F707 Change Step Selection 2 F708 Integral Output Power Retention F748 Integral Output Power Di...

Page 61: ...tion Main Power Under Voltage Alarm Stop After Instantaneous Power Off Alarm Stop After Lower Limit Continuous Time Light Load Alarm Heavy Load Alarm Maintenance Timer Alarm Over Torque Alarm Soft Stall Alarm Low Suction No Flow Cut Off Alarm Time Based Alternation Alarm Float Active Type Reset Type Reset Reset Selections F007 Real Time Clock Setup Set Real Time Clock N A Hours Minutes Seconds Mon...

Page 62: ...o ASD Overload Ratio DBR Dynamic Braking Resistor Overload Ratio Motor Load ASD Load DBR Dynamic Braking Resistor Load Input Power Output Power Changed From Default Display Changed Parameters N A Contrast Contrast Adjustment N A Main Monitor Selections 4 digit LED Display Item N A 4 digit LED Display Item while in Virtual Linear Pump Mode Monitor 1 Monitor 2 Trace Trace Selection F740 Program Mode...

Page 63: ... Reverse DC Braking Priority F253 Motor Shaft Stationary Control F254 Dynamic Braking not used Dynamic Braking Enable F304 Dynamic Braking Resistance F308 Continuous Dynamic Braking Capacity F309 Braking Resistance Overload Time 10x Rated Torque F639 Emergency Off Settings Emergency Off F603 Emergency DC Braking Control Time F604 Low Current Settings Low Current Trip F610 Low Current Detection Cur...

Page 64: ...y Restart Auto Restart F301 Number of Times to Retry F303 Ridethrough Time F310 Random Mode F312 Stall Over Voltage Limit Operation F305 Regenerative Over Excitation Upper Limit F319 Stall Prevention Factor 1 F416 Stall Prevention Level F601 Over Voltage Limit Operation Level F626 Over Voltage Limit Constant F469 Trip Settings Retain Trip Record at Power Down F602 Under Voltage Ridethrough Regener...

Page 65: ...65 UP DOWN Down Response Time F266 UP DOWN Down Frequency Step F267 Initial UP DOWN Frequency F268 Initial UP DOWN Frequency Rewriting F269 V I Settings Optional V I Terminal Voltage Current Selection F109 Preset Speeds Preset Speed 1 F018 Preset Speed 2 F019 Preset Speed 3 F020 Preset Speed 4 F021 Preset Speed 5 F022 Preset Speed 6 F023 Preset Speed 7 F024 Preset Speed 8 F287 Preset Speed 9 F288 ...

Page 66: ...F219 RX2 Input Point 1 Setting F222 RX2 Input Point 1 Frequency F223 RX2 Input Point 2 Setting F224 RX2 Input Point 2 Frequency F225 BIN Input Point 1 Setting F228 BIN Input Point 1 Frequency F229 BIN Input Point 2 Setting F230 BIN Input Point 2 Frequency F231 PG Input Point 1 Setting F234 PG Input Point 1 Frequency F235 PG Input Point 2 Setting F236 PG Input Point 2 Frequency F237 V I Input Bias ...

Page 67: ...t Setting Frequency 1 F190 V f 5 Point Setting Voltage 1 F191 V f 5 Point Setting Frequency 2 F192 V f 5 Point Setting Voltage 2 F193 V f 5 Point Setting Frequency 3 F194 V f 5 Point Setting Voltage 3 F195 V f 5 Point Setting Frequency 4 F196 V f 5 Point Setting Voltage 4 F197 V f 5 Point Setting Frequency 5 F198 V f 5 Point Setting Voltage 5 F199 Frequency Control Start Frequency F240 Run Frequen...

Page 68: ...n F721 Panel Frequency Lock Out F730 Panel Cable Breakage Detection F731 Panel Emergency Off Lockout F734 Panel Reset Lockout F735 Panel Command Frequency Lockout F736 Panel Keys Operation F737 MOTOR Motor Set 2 Base Frequency 2 F170 Base Frequency Voltage 2 F171 Manual Torque Boost 2 F172 Motor Overload Protection Level 2 F173 PM Motor PM Motor Constant 1 D Axis Inductance F498 PM Motor Constant ...

Page 69: ...nt 2 Rate F221 Torque Limit Settings Power Running Torque Limit 1 F440 Power Running Torque Limit 1 Level F441 Regenerative Braking Torque Limit 1 F442 Regenerative Braking Torque Limit 1 Level F443 Constant Output Zone Torque Limit F454 FEEDBACK Drooping Control Drooping Gain F320 Speed at 0 Drooping Gain F321 Speed at F320 Drooping Gain F322 Drooping Insensitive Torque F323 Drooping Output Filte...

Page 70: ... PG Input Phases F376 PG Disconnection Detection F377 Current Control Proportional Gain F458 Speed Loop Proportional Gain F460 Speed Loop Stabilization Coefficient F461 Load Moment of Inertia 1 F462 Motor Oscillation Control F467 Stall Prevention Control Switching F468 Max Output Voltage Modulation Rate F495 Number of RP Terminal Input Pulses F378 PID Output Dead Band F379 MY FUNCTION My Function ...

Page 71: ...Function Assigned F917 My Function Unit 4 Input Function Target 1 F935 Input Function Command 1 F936 Input Function Target 2 F937 Input Function Command 2 F938 Input Function Target 3 F939 Output Function Assigned F940 My Function Unit 5 Input Function Target 1 F941 Input Function Command 1 F942 Input Function Target 2 F943 Input Function Command 2 F944 Input Function Target 3 F945 Output Function...

Page 72: ...3 My Function Frequency Data 2 F924 My Function Frequency Data 3 F925 My Function Frequency Data 4 F926 My Function Frequency Data 5 F927 My Function Time Data 1 F928 My Function Time Data 2 F929 My Function Time Data 3 F930 My Function Time Data 4 F931 My Function Time Data 5 F932 My Function Count Data 1 F933 My Function Count Data 2 F934 My Function Analog Analog Input Function Target 11 F959 A...

Page 73: ...t Action 2 Wire and 4 Wire RS485 F804 Send Delay Time 2 Wire RS485 F805 ASD to ASD Communication 2 Wire RS485 F806 Communication Protocol 2 wire RS485 F807 Communication 1 Time Out Condition F808 Baud Rate 4 wire RS485 F820 Parity 4 wire RS485 F827 Send Delay Time 4 wire RS485 F825 ASD to ASD Communication 4 wire RS485 F826 Communication Protocol 4 wire RS485 F829 Free Notes F880 Network Option Re...

Page 74: ... Data 1 F581 Subnet Mask Data 2 F582 Subnet Mask Data 3 F583 Subnet Mask Data 4 F584 IP Gate 1 Data 1 F585 IP Gate 1 Data 2 F586 IP Gate 1 Data 3 F587 IP Gate 1 Data 4 F588 IP Master Data 1 F589 IP Master Data 2 F590 IP Master Data 3 F591 IP Master Data 4 F592 I O Scan Permission F593 Communication Time Out Modbus F594 MAC Address 1 F784 MAC Address 2 F785 MAC Address 3 F786 MAC Address 4 F787 MAC...

Page 75: ...8 Command Station Modbus F819 Communication Options Communication Option Setting 1 F830 Communication Option Setting 2 F831 Communication Option Setting 3 F832 Communication Option Setting 4 F833 Communication Option Setting 5 F834 Communication Option Setting 6 F835 Communication Option Setting 7 F836 Communication Option Setting 8 F837 Communication Option Setting 9 F838 Communication Option Set...

Page 76: ...ended Time F850 ASD Operation at Disconnection F851 Preset Speed Operation F852 Communication Option Station Address Monitor F853 Communication Option Speed Switch Monitor DeviceNet CC Link F854 PASSWORD AND LOCK OUTS Password Lock Outs Enter Password N A Change Password N A Lock Outs N A Program Mode Menu Navigation Primary Menu Sub Menu Parameter Name Parameter Number assword nd Lockout Buy www ...

Page 77: ...uency range The voltage and frequency specifications for a given motor may be found on the nameplate of the motor Settings 0 200 v 50 Hz 1 200 v 230 v 60 Hz 2 380v 480v 50 60 Hz 2 Upper Limit Frequency This parameter sets the highest frequency that the Q9 Plus ASD will accept as a frequency command or frequency setpoint The Q9 Plus ASD may output frequencies greater than the Upper Limit Frequency ...

Page 78: ...eleration screen as shown below 5 Volts Per Hertz Control Type This function establishes the relationship between the output voltage and the output frequency of the ASD Settings 0 Constant Torque 1 Voltage Decrease Curve 2 Automatic Torque Boost 3 Sensorless Vector Control speed 5 V f 5 Point Setting open 5 point setting window 6 PM Drive 7 PG Feedback Vector Control speed 9 Energy Saving 10 Advan...

Page 79: ... 3 RS485 4 wire Terminal Board 4 Communication Option Board 9 Frequency Command Source This selection establishes the source of the Frequency speed command Settings 1 V I 2 RR 3 RX 4 Panel Keypad 5 RS485 2 wire EOI Keypad 6 RS485 4 wire Terminal Board 7 Communication Option Board 8 RX2 9 Option V I 10 UP DOWN Frequency 11 Optional RP Pulse Input 12 Optional High Speed Pulse Input 10 Display Units ...

Page 80: ... of the Startup Wizard The basic parameters of the Q9 Plus ASD have been set Click Exit to load the Startup Wizard input and to return to the Frequency Command screen Additional application specific programming may be required Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 81: ...e set to 255 Setup to accept changes to the Virtual Linear Pump parameter settings Upon completion of the parameter changes set parameter F390 to 1 Direct Mode or 2 Process Hold to use the new settings for normal Virtual Linear Pump operations Zero may be selected at F390 to save the changes to be used later The setup procedure and the Wizard setup screens are shown below Figure 29 Input the Elect...

Page 82: ... Maximum Threshold 15 The Minimum threshold value setting is typically above the electrical stall of the motor above the minimum system pressure above the manual change plateau and well below the typical operating point of the system Click in the Minimum threshold field and using the Rotary Encoder slowly decrease the Minimum threshold value while observing the LED display If either of the conditi...

Page 83: ...le at zero Hz 18 Press the ESC key until reaching the Frequency Command screen 19 From the Frequency Command screen press ESC and scroll to the Control field Select Direct Mode if using no feedback if using feedback go to Step 22 on pg 75 20 While in the Hand mode press Run 21 While running adjust parameters F500 and F501 to stabilize operation if unstable Press ESC Buy www ValinOnline com Phone 8...

Page 84: ...en press ESC and scroll to the Control field Select Process Hold if using feedback if not using feedback go to Step 19 on pg 74 23 While in the Hand mode press Run 24 During operation adjust parameters F500 and F501 to stabilize operation if unstable Press ESC Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 85: ...work for the ASD being configured 2 Set parameter F827 to 0 No Parity 3 Set parameter F829 to 2 BACnet 4 Set parameter F899 to Reset Option Board and ASD The Q9 Plus ASD is now configured to communicate with the BACnet network S4 Pinout The S4 RJ 45 connector is located on the Terminal Board and is used for serial communications connectivity In order to use the S4 connector for serial communicatio...

Page 86: ...of the S4 input terminal Emergency Off NC On Off R LI5 Binary Input 14 BI14 LI5 Status Monitors the status of the LI5 input terminal On Off R LI6 Binary Input 15 BI15 LI6 Status Monitors the status of the LI6 input terminal On Off R LI7 Binary Input 16 BI16 LI7 Status Monitors the status of the LI7 input terminal On Off R LI8 Binary Input 17 BI17 LI8 Status Monitors the status of the LI8 input ter...

Page 87: ...is input C Commandable Table 6 BACnet Binary Values Binary Value Object ID Object Name Description Status Access Binary Value 0 BV0 Run Stop Status Indicates the running status of the drive Runs Ready R Binary Value 1 BV1 Fwd Rev Status Indicates the rotation direction of the drive Rev Fwd R Binary Value 2 BV2 Fault Status Indicates the fault status of the drive Faulted None R Binary Value 4 BV4 H...

Page 88: ...alog Inputs Analog Input Terminal Analog Input Object ID Object Name Description Value Access RR Analog Input 0 AI0 RR Level Input level of the RR analog input Percent of full scale R V I Analog Input 1 AI1 V I Level Input level of the V I analog input Percent of full scale R RX Analog Input 2 AI2 RX Level Input level of the RX analog input Percent of full scale R AI1 Analog Input 3 AI3 AI1 Level ...

Page 89: ...nalog Values Analog Value Object ID Object Name Description Value Access Analog Value 0 AV0 Output Speed Output speed output frequency base frequency x motor nameplate rpm ie 30 60 x 1770 885 RPM R Analog Value 1 AV1 Output Freq Frequency output Hz R Analog Value 2 AV2 DC Bus Volt DC bus voltage V R Analog Value 3 AV3 Output Volt Voltage output to the motor V R Analog Value 4 AV4 Output Current Cu...

Page 90: ...ommand reference C Analog Value 16 AV16 Freq Ref Frequency reference Hz C Analog Value 18 AV18 Last Flt Current fault code R Analog Value 19 AV19 Prev Flt 1 Most recent fault code R Analog Value 20 AV20 Prev Flt 2 Second most recent fault code R Analog Value 23 AV23 Accel Time 1 Changes Acceleration Time 1 F009 Sec W Analog Value 24 AV24 Decel Time 1 Changes Deceleration Time 1 F010 Sec W Refer to...

Page 91: ... require that the ASD input power be removed and then re applied for the changes to take affect Direct Access Parameters Numbers Automatic Acceleration Deceleration Program Fundamental Accel Decel 1 Settings This parameter is used to enable acceleration and deceleration rates in accordance with the applied load automatically The adjusted acceleration and deceleration times range from 12 5 to 800 o...

Page 92: ...ard Mode Selection The Frequency Mode 1 setting establishes the source of the frequency control input for the ASD The Frequency Mode 2 setting or the Override feature may supersede the Frequency Mode 1 setting Note Only Bolded items from the Settings list below may be placed in the Override Mode See the section titled Command Mode and Frequency Mode Control on pg 36 for additional information on t...

Page 93: ...stor To read Current at this terminal connect a 100 500 resistor in series from FM through the current meter to CC FM Terminal Setup Parameters F005 Set FM Function F006 Calibrate FM Terminal F681 Voltage Current Output Switching Selection F682 Output Response Polarity Selection F683 Set Zero Level Direct Access Number F005 Parameter Type Selection List Factory Default Output Frequency Changeable ...

Page 94: ...er Type Selection List Factory Default None Changeable During Run No Forward Reverse Run Program Fundamental Standard Mode Selection While operating in the Hand mode this parameter sets the direction of motor rotation From the Frequency Command screen press the ESC key At the subsequent EOI Command screen select the Direction field and change the setting Press the Rotary Encoder and the new settin...

Page 95: ...z for the Deceleration 1 profile The Accel Decel Pattern may be set using F502 Note A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads Automatic Accel Decel Stall and Ridethrough settings may lengthen the deceleration times Direct Access Number F010 Parameter Type Numerical Factory Default ASD Dependent Changeable During Run Yes Minimum ...

Page 96: ...ter Type Numerical Factory Default ASD Dependent Changeable During Run No Minimum ASD Dependent Maximum ASD Dependent Units Hz V f Pattern Program Fundamental Frequency Settings This function establishes the relationship between the output frequency and the output voltage The Automatic Torque Boost and the Sensorless Vector Control selections use the motor tuning parameters of the ASD to properly ...

Page 97: ...n Program Protection Overload This parameter is used to enable the Soft Stall feature which protects the motor from an over current condition by reducing the output frequency during a temporary increased current requirement from the load A V f motor may be specified here along with the Overload Stall to better match the ASD to the application This parameter setting may extend the Over Voltage Stal...

Page 98: ...plied to S1 S4 of the Terminal Board to run the associated Preset Speed If bidirectional operation is required F and R must be connected to CC With S1 being the least significant bit of a binary count the S1 S4 settings will produce the programmed speed settings as indicated in the Preset Speed Truth Table to the right Direct Access Number F018 Parameter Type Numerical Factory Default 0 00 Changea...

Page 99: ... number is applied to S1 S4 of the Terminal Board to output the Preset Speed See F018 for additional information on this parameter Direct Access Number F022 Parameter Type Numerical Factory Default 0 00 Changeable During Run Yes Minimum Lower Limit Freq F013 Maximum Upper Limit Freq F012 Units Hz Preset Speed 6 Program Frequency Preset Speeds This parameter assigns an output frequency to binary nu...

Page 100: ...s to change the settings individually Settings 0 Disabled 1 RR 2 V I 3 Select RR or V I by TB Terminal Board 4 Keypad Frequency and Command from TB Terminal Board 5 Keypad Frequency and Command 6 Coast Stop Direct Access Number F040 Parameter Type Selection List Factory Default Disabled Changeable During Run No User Selections 0 1 2 3 4 5 6 Related Params Default Settings Disabled RR V I RR or V I...

Page 101: ... Maximum Upper Limit Freq F012 Units Hz Speed Reach Detection Band Program Terminal Reach Settings This parameter sets the bandwidth of the Speed Reach Frequency F101 setting Direct Access Number F102 Parameter Type Numerical Factory Default ASD Dependent Changeable During Run Yes Minimum 0 00 Maximum Upper Limit Freq F012 Units Hz Forward Reverse Run Priority When Both Are Closed Program Terminal...

Page 102: ...tion is used with the Expansion IO Card Option P N ETB004Z This parameter defines the format of the binary or BCD data when using the option card Note The Expansion IO Card Option 2 option board is required to use this terminal See the Expansion IO Card Option 1 instruction manual P N 58685 for additional information on the function of this terminal Settings 0 None 1 12 Bit Binary 2 16 Bit Binary ...

Page 103: ...No Input Terminal 1 F Function Program Terminal Input Terminals This parameter is used to set the functionality of the F discrete input terminal In addition this input terminal must be specified as Normally Open or Normally Closed This parameter sets the programmable F terminal to one of the user selectable functions listed in Table 10 on pg 234 Direct Access Number F111 Parameter Type Selection L...

Page 104: ...dition this input terminal must be specified as Normally Open or Normally Closed This parameter sets the programmable S2 terminal to one of the user selectable functions listed in Table 10 on pg 234 Direct Access Number F116 Parameter Type Selection List Factory Default Preset Speed 2 Changeable During Run No Input Terminal 7 S3 Function Program Terminal Input Terminals This parameter is used to s...

Page 105: ...n of the programmable LI2 terminal to one of the user selectable functions listed in Table 10 on pg 234 Note The Expansion IO Card Option 1 option board P N ETB003Z is required to use this terminal See the Expansion IO Card Option 1 instruction manual P N 58685 for additional information on the function of this terminal Direct Access Number F120 Parameter Type Selection List Factory Default Unassi...

Page 106: ...on of the programmable LI5 terminal to one of the user selectable functions listed in Table 10 on pg 234 Note The Expansion IO Card Option 2 option board P N ETB004Z is required to use this terminal See the Expansion IO Card Option 2 instruction manual P N 58686 for additional information on the function of this terminal Direct Access Number F123 Parameter Type Selection List Factory Default Unass...

Page 107: ...ber F126 Parameter Type Selection List Factory Default Unassigned Changeable During Run No Always ON Terminal Function 2 Program Terminal Input Terminals This parameter is used to set the functionality of the virtual discrete input terminal Always ON Terminal Function 2 As a virtual terminal this control terminal exists only in memory and is considered always to be in its True connected to CC stat...

Page 108: ...ection List Factory Default Acceleration Deceleration Completion Changeable During Run No Output Terminal 3 FL Function Program Terminal Output Terminals This parameter is used to set the functionality of the FL output terminals to one of the user selectable functions listed in Table 13 on pg 239 In addition the output terminals must be specified as Normally Open or Normally Closed Direct Access N...

Page 109: ...on of the programmable R1 terminal to one of the user selectable functions listed in Table 13 on pg 239 Note The Expansion IO Card Option 1 option board P N ETB003Z is required to use this terminal See the Expansion IO Card Option 1 instruction manual P N 58685 for additional information on the function of this terminal Direct Access Number F135 Parameter Type Selection List Factory Default Always...

Page 110: ... terminal In addition this output terminal must be specified as Normally Open or Normally Closed This setting assigns the function of the programmable R2 terminal to one of the user selectable functions listed in Table 13 on pg 239 Note The Expansion IO Card Option 2 option board P N ETB004Z is required to use this terminal See the Expansion IO Card Option 2 instruction manual P N 58686 for additi...

Page 111: ...d value see waveforms at F140 The delay may be increased to provide additional electrical noise immunity or to prevent the ASD from responding to contact bounce or chatter Direct Access Number F144 Parameter Type Numerical Factory Default 8 Changeable During Run No Minimum 2 Maximum 200 Units mS Input Terminal 13 20 Response Time Program Terminal Input Terminal Delays This parameter delays the res...

Page 112: ...Hz Base Frequency Voltage 2 Program Motor Motor Set 2 The Base Frequency Voltage 2 setting is the Motor 2 output voltage at the Base Frequency F170 Regardless of the programmed value the output voltage cannot be higher than the input voltage The actual output voltage will be influenced by the input voltage of the ASD and the Supply Voltage Compensation setting F307 This parameter is used only when...

Page 113: ...set to A V rather than Direct Access Number F173 Parameter Type Numerical Factory Default 100 Changeable During Run Yes Minimum 10 Maximum 100 Units V f 5 Point Setting Frequency 1 Program Special V f 5 Point Setting The V f 5 Point Setting Frequency 1 setting establishes the frequency that is to be associated with the voltage setting of F191 V f 5 Point Setting Voltage 1 The V f 5 Point settings ...

Page 114: ...15 volt actual output for the 230 volt ASD of the full display range If using as a unit of measure and with no voltage correction F307 Disabled the ASD output voltage will be the percentage setting times 230 for the 230 volt unit or times 460 volts for the 460 volt unit See F190 for additional information on this parameter Direct Access Number F191 Parameter Type Numerical Factory Default 0 0 Chan...

Page 115: ...ing Frequency 3 The F701 parameter setting will determine if the selection for this parameter appears in the form of a Voltage V or as a Percentage of the ASD rating The default setting is See F190 and F191 for additional information on this parameter Direct Access Number F195 Parameter Type Numerical Factory Default 0 0 Changeable During Run No Minimum 0 0 Maximum 100 0 Units V or F701 V f 5 Poin...

Page 116: ...cy Mode 2 may control the output frequency of the ASD This parameter determines which of the two will control the output frequency and the conditions in which control will be switched from one to the other Note Frequency Mode is abbreviated as FMOD The Frequency Mode 1 or Frequency Mode 2 selection specifies the source of the input frequency command signal These selections are performed at F004 an...

Page 117: ...l Set V I Input Point 1 Frequency F202 Set V I Input Point 1 Setting F201 the input analog signal level that corresponds to the frequency setting at V I Input Point 1 Frequency Set V I Input Point 2 Frequency F204 Set V I Input Point 2 Setting F203 the input analog signal level that corresponds to the frequency setting at V I Input Point 2 Frequency Provide a Run command F and or R Once set as the...

Page 118: ...ting in the Speed control mode or is associated with the V I Input Point 1 Rate when operating in the Torque Control mode This value is entered as 0 to 100 of the V I input signal range See V I Input Point 1 Setting F201 for additional information on this parameter when used for Speed control See V I Input Point 1 Rate F203 for additional information on this parameter when used for Torque Control ...

Page 119: ...e torque setting at V I Input Point 1 Rate Set V I Input Point 2 Rate F206 Set V I Input Point 2 Setting F203 the input analog signal level that corresponds to the torque setting at V I Input Point 2 Rate Provide a Run command F and or R Torque Control is accomplished by establishing an associated V f output pattern for a given V I input level Once set as the V I input voltage changes or the V I c...

Page 120: ...and signal to be used as Frequency Mode 2 in the event that Frequency Mode 1 is disabled or if Frequency Mode 2 is set up as the primary control parameter See F004 and F200 for additional information on this parameter Settings 1 V I 2 RR 3 RX 4 Panel Keypad 5 RS485 2 Wire EOI 6 RS485 4 Wire Terminal Board 7 Communication Option Board 8 RX2 9 Option V I 10 UP DOWN Frequency 11 Optional RP Pulse Inp...

Page 121: ...f the ASD If the filtering selection Small is selected the ASD averages the last 8 mS of sampled signal and converted digital values The rolling average is updated every 4 µS and scaled for use by the microprocessor This holds true for the Medium Large and Huge selections providing a larger sample to produce the average for use by the microprocessor False responses to electrical noise are eliminat...

Page 122: ...o receive Speed control input at the RR input terminal Program Fundamental Standard Mode Selection Frequency Mode 1 RR Program Fundamental Standard Mode Selection Command Mode Selection Terminal Board Provide a Run command F and or R Once set as the RR input voltage changes the output frequency of the ASD will vary in accordance with the above settings This parameter value is entered as 0 to 100 o...

Page 123: ...214 for additional information on this parameter when used for Torque Control Direct Access Number F212 Parameter Type Numerical Factory Default 100 Changeable During Run Yes Minimum 0 Maximum 100 Units RR Input Point 2 Frequency Program Frequency Speed Reference Setpoints This parameter is used to set the gain and bias of the RR input terminal when the RR terminal is used as the control input whi...

Page 124: ...he RR input voltage changes the output torque of the ASD will vary in accordance with the above settings This parameter sets RR Input Point 1 Rate and is the output torque value that is associated with the setting of RR Input Point 1 Setting when operating in the Torque Control mode This value is entered as 0 to 250 of the rated torque Direct Access Number F214 Parameter Type Numerical Factory Def...

Page 125: ...Frequency F219 Set RX Input Point 2 Setting F218 the input analog signal level that corresponds to the speed setting at RX Input Point 2 Frequency Provide a Run command F and or R Once set as the RX input voltage changes the ASD output speed and or torque will vary in accordance with the above settings This parameter value is entered as 100 to 100 of the RX input signal range See F474 and F475 for...

Page 126: ...0 for additional information on this parameter when used for Torque Control Direct Access Number F218 Parameter Type Numerical Factory Default 100 Changeable During Run Yes Minimum 100 0 Maximum 100 0 Units RX Input Point 2 Frequency Program Frequency Speed Reference Setpoints This parameter is used to set the gain and bias of the RX input terminal when the RX terminal is used as the control input...

Page 127: ...ut voltage changes the ASD output speed and or torque will vary in accordance with the above settings This parameter sets RX Input Point 1 Rate and is the output torque value that is associated with the setting of RX Input Point 1 Setting when operating in the Torque Control mode This value is entered as 250 to 250 of the rated torque Direct Access Number F220 Parameter Type Numerical Factory Defa...

Page 128: ... Speed Control Perform the following setup to allow the system to perform Speed control from the RX2 input terminal Set RX2 Input Point 1 Frequency F223 Set RX2 Input Point 1 Setting F222 the input analog signal level that corresponds to the speed setting at RX2 Input Point 1 Frequency Set RX2 Input Point 2 Frequency F225 Set RX2 Input Point 2 Setting F224 the input analog signal level that corres...

Page 129: ...ociated with RX2 Input Point 2 Frequency when operating in the Speed control mode or is associated with the RX2 Input Point 2 Rate when operating in the Torque Control mode This value is entered as 100 to 100 of the RX2 input signal range See RX2 Input Point 1 Setting F222 for additional information on this parameter when used for Speed control Direct Access Number F224 Parameter Type Numerical Fa...

Page 130: ...e terminal will transfer the status of the Binary Bit s 0 7 or 0 MSB to the control board for speed control Speed Control Perform the following setup to allow the system to perform Speed control from the BIN input terminals Set BIN Input Point 1 Frequency F229 Set the BIN input value of 255D F228 that represents BIN Input Point 1 Frequency Set BIN Input Point 2 Frequency F231 Set the BIN input val...

Page 131: ...rameter sets the BIN input signal that is associated with BIN Input Point 2 Frequency This value is entered as 0 to 100 of the BIN input signal range See BIN Input Point 1 Setting F228 for additional information on this parameter Direct Access Number F230 Parameter Type Numerical Factory Default 100 Changeable During Run Yes Minimum 0 Maximum 100 Units BIN Input Point 2 Frequency Program Frequency...

Page 132: ...esents PG Point 2 Frequency Once set as the PG input pulse count rate changes the output frequency of the ASD will vary in accordance with the above settings This parameter sets the PG input pulse count that represents Reference Setpoint 1 frequency The range of values for this parameter is 0 to 100 of the PG input pulse count range Note Further application specific PG settings may be performed fr...

Page 133: ...he ASD will accelerate to the programmed setting Output frequencies below the Start Frequency will not be output from the ASD during startup However once reaching the Start Frequency speed values below the Start Frequency may be output from the ASD If the setting of this parameter results in an over current condition at startup reduce the setting of this parameter to a value less than the rated sl...

Page 134: ...aking will start DC Injection Braking DC Injection Braking is a braking system used with 3 phase motors Unlike conventional brakes there is no physical contact between the rotating shaft and a stationary brake pad or drum When braking is required the ASD outputs a DC current that is applied to the windings of the motor to quickly brake the motor The braking current stops when the time entered in F...

Page 135: ...njection brake stops the motor and continues until ST CC is opened power is turned off an Emergency Off command is received or this parameter is changed Enabling this feature will also require a non zero entry at F250 Settings 0 Disabled 1 Enabled Direct Access Number F254 Parameter Type Selection List Factory Default Disabled Changeable During Run Yes 0 Hz Command Output Program Special Special P...

Page 136: ...up and Execution To initiate a Jog Run from the EOI perform the following 1 Set the Command Mode Selection F003 to Panel Keypad This setting places the ASD in the Auto mode 2 Set the Frequency Mode Selection F004 to Panel Keypad 3 Enable the Jog function F262 4 Set the Input Terminal Priority F106 function to Enable to receive Jog commands 5 Assign the Jog Run setting to any unused discrete input ...

Page 137: ...eceleration Changeable During Run No Panel Operation Jog Mode Program Frequency Jog Settings This parameter enables the Jog command to be received from the EOI When disabled the Jog command received from the EOI is ignored Jog commands may also be received from the Terminal Board Priority as to which is allowed to override the other is selected at F106 The priority selection at F106 enables the se...

Page 138: ...ed Set one unused discrete input terminal to UP DOWN Frequency up and one unused discrete input terminal to UP DOWN Frequency down F264 Sets the system response delay to the initial activation of the discrete input terminal UP DOWN Frequency up Also sets the response delay of subsequent terminal activations of the UP DOWN Frequency up terminal during an activate and hold F265 Sets the frequency in...

Page 139: ...UP DOWN Frequency down terminal activation The rate of the frequency decrease is set at Deceleration Time 1 F010 See F264 for additional information on this parameter Direct Access Number F267 Parameter Type Numerical Factory Default ASD Dependent Changeable During Run Yes Minimum 0 00 Maximum Maximum Freq F011 Units Hz Initial UP DOWN Frequency Program Frequency UP DOWN Frequency Functions At pow...

Page 140: ... the Jump Frequency range and continue upward as programmed During deceleration the output frequency of the ASD will hold at the upper level of the Jump Frequency range until the programmed deceleration ramp reaches the lower level of the Jump Frequency range at which time the output frequency of the ASD will decelerate to the lower level of the Jump Frequency range and continue downward as progra...

Page 141: ...requency 3 Program Special Jump Frequencies This parameter is the same as Jump Frequency 1 F270 and is used when multiple frequencies are to be jumped see the plus or minus value setting at F275 When multiple jump frequencies overlap the system will recognize the lowest and the highest frequencies as one jump range Direct Access Number F274 Parameter Type Numerical Factory Default 0 00 Changeable ...

Page 142: ...uring Run Yes Minimum Lower Limit Freq F013 Maximum Upper Limit Freq F012 Units Hz Preset Speed 12 Program Frequency Preset Speeds This parameter assigns an output frequency to binary number 1100 and is identified as Preset Speed 12 The binary number is applied to S1 S4 of the Terminal Board to output the Preset Speed See F018 for additional information on this parameter Direct Access Number F291 ...

Page 143: ...it cannot be decreased below 2 0 kHz while running If the PWM carrier frequency is set at 1 9 kHz or below it cannot be increased above 2 0 kHz while running Either change requires that the ASD be stopped and restarted for the changes to take effect Direct Access Number F300 Parameter Type Numerical Factory Default ASD Dependent Changeable During Run Yes Minimum ASD Dependent Maximum ASD Dependent...

Page 144: ... duration of the Ridethrough it is not used to drive the motor The motor s of the system are stopped and then restarted automatically if so configured Note If used to restart the motors the Retry setup of F301 is required Settings 0 Off 1 Ridethrough 2 Deceleration Stop Ridethrough Setup Requirements 1 Select the Ridethrough Mode at F302 2 Select the Ridethrough Time at F310 Direct Access Number F...

Page 145: ...Earth Fault Ground Fault Over Current During Acceleration Arm Over Current at Start Up DBR Resistor Over Current Low Current Voltage Drop In Main Circuit EEPROM Data Fault EEPROM Fault Flash Memory Gate Array RAM ROM Fault CPU Fault Emergency Off Communication Error Option Fault Sink Source Setting Error Over Speed Error Over Torque Key Error External Thermal Error Externally Controlled Interrupt ...

Page 146: ... PA to PB of the ASD and providing the proper information at F304 F308 and F309 Direct Access Number F304 Parameter Type Selection List Factory Default Off Changeable During Run No Over Voltage Limit Operation Program Protection Stall This parameter enables the Over Voltage Limit function This feature in conjunction with the setting of F626 is used to set the upper DC bus voltage threshold that on...

Page 147: ...too low may result in system damage Direct Access Number F308 Parameter Type Numerical Factory Default ASD Dependent Changeable During Run No Minimum 0 5 Maximum 1000 0 Units Continuous Dynamic Braking Capacity not used Program Protection Dynamic Braking This parameter is used to input the wattage of the Dynamic Braking Resistor Note Using a resistor with a wattage rating that is too low may resul...

Page 148: ... parameter provides for the automatic decrease of the carrier frequency Select 1 to decrease the Carrier Frequency setting as a function of an increased current requirement Selection 2 or 3 may also include an output voltage drop as a function of an increased current requirement The Carrier Frequency should be set below 4 kHz Settings 0 No Decrease and No Limit 1 Valid Decrease and No Limit 2 No D...

Page 149: ...nically coupled motors Direct Access Number F320 Parameter Type Numerical Factory Default 0 0 Changeable During Run Yes Minimum 0 0 Maximum 100 0 Units Speed at 0 Drooping Gain Program Feedback Drooping Control This parameter sets the motor speed when at the 0 output torque gain while operating in the Drooping Control mode This function determines the lowest speed that Drooping will be in effect f...

Page 150: ... of output change allowed when operating in the Drooping Control mode Jerky operation may be reduced by increasing this setting Direct Access Number F324 Parameter Type Numerical Factory Default 100 0 Changeable During Run Yes Minimum 0 1 Maximum 200 0 Units RAD F324 F324 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 151: ... power switching Once timed out the motor resumes normal commercial power operation Settings 0 Off 1 Switch at Signal Input and Trip 2 Switch at Signal Input with Switching Frequency 3 Switch at Signal Input and Trip with Switching Frequency Switching Setup Requirements F354 Enable the switching function F355 Set the switching frequency F356 Speed Hold time before applying ASD output after the swi...

Page 152: ...ram Terminal Line Power Switching This parameter determines the amount of time that the ASD will wait before allowing commercial power to be applied to the motor once the switch to commercial power criteria has been met See F354 for additional information on this parameter Direct Access Number F357 Parameter Type Numerical Factory Default 0 62 Changeable During Run Yes Minimum 0 40 Maximum 10 00 U...

Page 153: ...m 0 0 Maximum 25 0 PID Feedback Proportional P Gain Program Feedback Feedback Settings This parameter determines the degree that the Proportional function affects the output signal The larger the value entered here the quicker the ASD responds to changes in feedback Direct Access Number F362 Parameter Type Numerical Factory Default 50 00 Changeable During Run Yes Minimum 0 01 Maximum 100 00 PID Fe...

Page 154: ...imum Upper Limit Freq F012 Units Hz Process Lower Limit Program Feedback Feedback Settings Selecting Process PID at parameter F359 allows for this parameter setting to function as the Lower Limit while operating in the PID Control mode Direct Access Number F368 Parameter Type Numerical Factory Default Lower Limit Freq F013 Changeable During Run Yes Minimum Lower Limit Freq F013 Maximum Upper Limit...

Page 155: ...Parameter Type Numerical Factory Default 10 0 Changeable During Run Yes Minimum 0 1 Maximum 600 0 Units Seconds Frequency Command Detection Range Program Feedback Feedback Settings While operating in the PID mode this parameter reads the feedback frequency Once the feedback frequency is within the setting of this parameter F374 relative to the commanded frequency a properly configured output termi...

Page 156: ...In conjunction with parameter settings F234 F237 this parameter is used to scale the input pulse train speed control signal when using the optional Expansion IO Card Option 2 When using the optional terminal board the frequency command can be input via the pulse train input RP The input pulse frequency is calculated to the percent base data which is then converted to the frequency based on setting...

Page 157: ...upon operating for a user set amount of time within the Virtual Linear Pump Minimum Threshold threshold See F383 and F480 for additional information on this parameter Settings 0 Disabled 1 Enabled Direct Access Number F382 Parameter Type Selection List Factory Default Disabled Changeable During Run Yes Virtual Linear Pump Sleep Delay Timer Program Virtual Linear Pump Sleep Timer During a properly ...

Page 158: ...to minimize system responses to rapid fluctuations in the feedback signal See F385 for additional information on this parameter Direct Access Number F387 Parameter Type Numerical Factory Default 5 0 Changeable During Run Yes Minimum 0 1 Maximum 6553 5 Units Seconds Virtual Linear Pump Low Start Stop Point Program Virtual Linear Pump Start and Stop Points During a properly configured Virtual Linear...

Page 159: ...figured Virtual Linear Pump operation this parameter establishes if feedback is used or not Select the command source or the feedback source for operating in the Direct or Process modes respectively at F396 The default selection for each may be used Note If F396 is set to use V I as the command source DO NOT set this parameter to Process Hold Doing so will result in an error message V I cannot be ...

Page 160: ...a properly configured Virtual Linear Pump operation this parameter establishes the minimum setpoint within the Virtual Linear Pump operating domain Direct Access Number F394 Parameter Type Numerical Factory Default 10 Changeable During Run Yes Minimum 10 Maximum Virtual Linear Pump Maximum Setting F395 Virtual Linear Pump Maximum Threshold Program Virtual Linear Pump Settings During a properly con...

Page 161: ...Linear Pump Low Frequency Limit Direct Access Number F398 Parameter Type Numerical Factory Default 15 00 Changeable During Run Yes Minimum 1 00 Maximum 60 00 Units Hz Autotune 1 Program Motor Vector Motor Model This parameter sets the Autotune command status Selecting Reset Motor Defaults for this parameter sets parameters F410 F411 F412 and F413 to the factory default settings If selecting Autotu...

Page 162: ...adjust the Autotune parameter values as a function of increases in the temperature of the motor Settings 0 Off 1 Self Cooled Motor Tuning 2 Forced Air Cooled Motor Tuning Direct Access Number F402 Parameter Type Selection List Factory Default Off Changeable During Run No Virtual Linear Pump Transducer Minimum Reading Program Virtual Linear Pump Settings During a properly configured Virtual Linear ...

Page 163: ...esults in the Lead pump being over worked and requiring more maintenance The TBA algorithm allows the user to set the time that each pump within the system is to be assigned the Lead pump function and which are assigned the function of being the Lag pump s Upon completion of the user set time the system changes the Lead pump assignment to the next pump number F434 The Virtual Linear Pump feature a...

Page 164: ...rload tripping Direct Access Number F410 Parameter Type Numerical Factory Default ASD Dependent Changeable During Run Yes Minimum 0 0 Maximum 30 0 Units Motor Constant 2 No Load Current Program Motor Vector Motor Model This parameter is used to set the current level required to excite the motor Specifying a value that is too high for this parameter may result in hunting erratic motor operation Dir...

Page 165: ... load occurs the motor may stall before the load current reaches the stall prevention level setting of F601 A drop in the supply voltage may cause fluctuations of the load current or may cause motor vibration A gradual adjustment of this parameter may alleviate this condition Start with a setting of 85 at these parameters and gradually adjust them from there one at a time until the desired results...

Page 166: ... List Factory Default Off Changeable During Run Yes Time Based Alternation Period Program Virtual Linear Pump Time Based Alternation During Time Based Alternation operation this parameter sets the time that the Lead ASD and Lag ASD assignments are valid until changed as a function of the Time Based Alternation settings Direct Access Number F418 Parameter Type Numerical Factory Default 1 Minute Cha...

Page 167: ...on while running in the Direct mode this parameter sets the time that the system may operate within the maximum or minimum Virtual Linear Pump zones before turning the ASD on or off respectively Direct Access Number F439 Parameter Type Numerical Factory Default 1000 Changeable During Run No Minimum 0 Maximum 65535 Units Seconds Power Running Torque Limit 1 Program Torque Torque Limit Settings This...

Page 168: ...s used in conjunction with the setting of parameter F483 If On Physical Switch or On Electronic Switch is selected at parameter F483 then this parameter selection sets the disposition of the system in the event of a Low Suction No Flow Cut Off condition that exists for the duration of the parameter F484 setting If Off is selected at parameter F483 then this parameter selection is ignored Settings ...

Page 169: ...60 Parameter Type Numerical Factory Default 12 Changeable During Run Yes Minimum 1 Maximum 9999 Speed Loop Stabilization Coefficient Program Feedback PG Settings During closed loop operation this parameter sets the response sensitivity of the ASD when monitoring the output speed for control The larger the value entered here the quicker the response to changes in the received feedback Direct Access...

Page 170: ...will cause an Over Voltage Stall While running or during deceleration the Over Voltage Stall function increases the output frequency of the ASD for a specified time in an attempt to prevent an Over Voltage Trip If the over voltage threshold level setting of parameter F626 is exceeded for over 4 mS an Over Voltage Trip will be incurred Select zero 0 for automatic value selection for this parameter ...

Page 171: ...y Default 128 Changeable During Run Yes Minimum 0 Maximum 255 RR Input Gain Program Frequency Speed Reference Setpoints This parameter is used to fine tune the gain of the RR input terminal when this terminal is used as the control input while operating in the Speed Control mode or the Torque Control mode This setting may be used to ensure that the 100 level of the input source pot pressure transd...

Page 172: ...erical Factory Default 128 Changeable During Run Yes Minimum 0 Maximum 255 RX2 Input Gain Program Frequency Speed Reference Setpoints This parameter is used to fine tune the gain of the RX2 input terminal when this terminal is used as the control input while operating in the Speed Control mode or the Torque Control mode This setting may be used to ensure that the 100 level of the input source pot ...

Page 173: ...Control mode This setting may be used to ensure that the 100 level of the input source pot pressure transducer flow meter etc is also the 100 level setting of the ASD system This is accomplished by setting the input source to 100 and adjusting this setting to provide an output of 100 from the ASD Direct Access Number F479 Parameter Type Numerical Factory Default 128 Changeable During Run Yes Minim...

Page 174: ... the External Device Delay Timer times out while OUT2 is activated OUT2 will change states and deactivate the second auxiliary pump Lag2 Should the system return to the Virtual Linear Pump Minimum Threshold for a duration in excess of the External Device Delay Timer OUT1 will change states and deactivate the auxiliary pump Lag1 Note Set the Sleep Timer Delay F383 to two 2 times the Virtual Linear ...

Page 175: ... pump or if there is a closed output valve at the pump output A low pressure suction switch may be used to detect the loss of feed water by opening or closing a circuit in the event of feed water loss The switch state change would result in the activation of a discrete input terminal set to Low Suction No Flow Protection resulting in an AbFL trip Either a closed output valve or a suction pressure ...

Page 176: ...ing water An external sealing water pump is required to supply sealing water and is enabled via an ASD output contactor set to Sealing Water Normal ASD operations are allowed once an adequate water supply is detected at the seal as detected by a pump mounted reed switch that is connected to a discrete input terminal of the ASD Set the discrete input terminal to Sealing Water Settings 0 Disabled 1 ...

Page 177: ...ical stress to loads Automatic Accel Decel Stall and Ridethrough settings may lengthen the acceleration times Direct Access Number F500 Parameter Type Numerical Factory Default 5 0 Changeable During Run Yes Minimum 0 1 Maximum 6000 0 Units Seconds Deceleration Time 2 Program Fundamental ACC DEC 1 4 Settings This parameter specifies the time in seconds for the output of the ASD to go from the Maxim...

Page 178: ...decel patterns Direct Access Number F502 Parameter Type Selection List Factory Default Linear Changeable During Run Yes Linear acceleration and deceleration is the default pattern and is used on most applications S pattern 1 is used for applications that require quick acceleration and deceleration This setting is also popular for applications that require shock absorption at the start of accelerat...

Page 179: ... includes a Switching Frequency setting F505 The Switching Frequency is used as a threshold frequency that once reached signals the ASD to switch to the other profile Acc Dec 1 is set up using parameters F009 Acc Time F010 Dec Time F502 Pattern and F505 Switching Frequency Acc Dec 2 is set up using parameters F500 Acc Time F501 Dec Time and F503 Pattern To switch using a discrete input terminal as...

Page 180: ... Data 1 Direct Access Number F577 Program Communications Ethernet Settings Parameter Type Numerical Selecting Manual at parameter F576 enables parameters F577 F580 to be used to create an IP address for the connected device This parameter is used to configure the IP Data Card 1 section of the IP address of the device Factory Default 00 Changeable During Run Yes Minimum 00 Maximum 255 IP Card Data ...

Page 181: ...1 This parameter is used to configure the Subnet Data Mask 2 section of the subnet mask for the device See F581 for additional information on this parameter Direct Access Number F582 Parameter Type Numerical Factory Default 00 Changeable During Run Yes Minimum 00 Maximum 255 Subnet Mask Data 3 Program Communications Ethernet Settings This parameter operates in conjunction with parameter F581 This ...

Page 182: ... 4 Program Communications Ethernet Settings See F585 for information on this parameter Direct Access Number F588 Parameter Type Numerical Factory Default 00 Changeable During Run Yes Minimum 00 Maximum 255 IP Master Data 1 Program Communications Ethernet Settings If using the option board IPE001Z this parameter is used in conjunction with parameters F589 F592 to configure the network Parameters F5...

Page 183: ...ut The communications network includes other ASDs and Host Control computers that monitor the status of the ASD s transfers commands and loads or modifies the parameter settings of the ASD Changes made to this parameter require that the power be cycled Off then On for the changes to take effect Direct Access Number F594 Parameter Type Numerical Factory Default 0 0 Changeable During Run Yes Minimum...

Page 184: ... Type Selection List Factory Default Disabled Changeable During Run Yes Emergency Off Mode Program Protection Emergency Off Settings This parameter determines the method used to stop the motor in the event that an Emergency Off command is received and the system is configured to use this feature This setting may also be associated with the FL terminals to allow the FL relay to change states when a...

Page 185: ...of the Overload Reduction function aides in minimizing the generated heat and precluding an Overload trip This function is useful in loads such as fans pumps and blowers that have the square reduction torque characteristic The default overload time is 300 seconds at 150 ASD output this time may vary as a function of the magnitude of the overload Direct Access Number F606 Parameter Type Numerical F...

Page 186: ...ime Program Protection Low Current Settings With the Low Current Trip F610 parameter enabled this function sets the time that the low current condition must exist to cause a trip Direct Access Number F612 Parameter Type Numerical Factory Default 0 Changeable During Run Yes Minimum 0 Maximum 255 Units Seconds Short Circuit Detection At Start Program Protection Special Protection Parameters This par...

Page 187: ...enerative Braking Program Protection Over Torque Parameters This parameter sets the torque threshold level that is used as a setpoint for over torque tripping during negative torque regen This setting is a percentage of the maximum rated torque of the ASD This function is enabled at F615 Direct Access Number F617 Parameter Type Numerical Factory Default 250 00 Changeable During Run Yes Minimum 0 0...

Page 188: ...ng Run Yes Minimum 0 01 Maximum 100 00 Units Seconds Over Speed Detection Frequency Upper Band Program Protection Abnormal Speed Settings This parameter sets the upper level of the Base Frequency range that once exceeded will cause an Over Speed Detected alert This parameter functions in conjunction with the settings of F622 and F624 Direct Access Number F623 Parameter Type Numerical Factory Defau...

Page 189: ...lt Disabled Changeable During Run No Under Voltage Trip Alarm Detection Time Program Protection Under Voltage Ridethrough This parameter sets the time that the under voltage condition must exist to cause an Under Voltage Trip This parameter is enabled at F627 Direct Access Number F628 Parameter Type Numerical Factory Default 0 03 Changeable During Run No Minimum 0 01 Maximum 10 00 Units Seconds Re...

Page 190: ...e V I input signal range Direct Access Number F633 Parameter Type Numerical Factory Default 0 Disabled Changeable During Run Yes Minimum 0 Maximum 100 Units Annual Average Ambient Temperature Program Special Special Parameters This parameter is used in conjunction with a discrete output terminal setting to notify the operator of the remaining useful life of critical components of the ASD system Wi...

Page 191: ...Card Option 2 A thermistor is connected from TH1 to TH1 of TB4 on the Expansion IO Card Option 2 Should the thermistor resistance reading fall below 50 because of an over temperature condition or exceed 3000 because of an open circuit an External Thermal Fault OH2 will be incurred Note While this parameter is Enabled the system cannot be restarted until the thermistor value recovers to the level o...

Page 192: ...s This parameter is used with synchronous motor applications only Contact the TIC Customer Support Center for information on this parameter Settings 0 No Wait Time for Frequencies Less Than 10 Hz 1 No Wait Time for Frequencies Less Than 20 Hz Direct Access Number F643 Parameter Type Selection List Factory Default No Wait Time for Frequencies Less Than 10 Hz Changeable During Run No Select Operatio...

Page 193: ...ype Numerical Factory Default 3000 Changeable During Run Yes Minimum 100 Maximum 9999 Units Forced Fire Speed Control Program Protection Fire Speed Control This parameter is used to enable the Forced Fire Speed function The Forced Fire Speed function runs Preset Speed 15 in the event of an emergency Preset Speed 15 must be configured to use the Forced Fire Speed function Settings 0 Disabled 1 Enab...

Page 194: ...Under Torque Detection Time Program Protection Under Torque Detection This parameter sets the time that the low torque condition must exist to activate the Under Torque disposition of the parameter F651 setting Direct Access Number F654 Parameter Type Numerical Factory Default 0 50 Changeable During Run Yes Minimum 0 00 Maximum 10 00 Units Seconds Under Torque Detection Hysteres Program Protection...

Page 195: ...r Enables Disables the feature that allows for the external adjustment of the commanded frequency Selecting either of the input methods listed enables this feature The selected input is used as a multiplier of the commanded frequency If Setting F729 is selected the value entered at parameter F729 is used as the multiplier of the commanded frequency Contact the TIC Customer Support Center for more ...

Page 196: ... adjust this parameter until the associated function of parameter F670 produces the desired DC level output at the AM output terminal See F670 for additional information on this parameter Direct Access Number F671 Parameter Type Numerical Factory Default 154 Changeable During Run Yes Minimum 1 Maximum 1280 MON 1 Terminal Meter Selection Program Terminal Analog Output Terminals This parameter is us...

Page 197: ...justment F691 MON2 Voltage Current Output Switching F692 MON2 Output Gradient Characteristic F693 MON2 Bias Adjustment Set Zero Level Direct Access Number F674 Parameter Type Selection List Factory Default Output Frequency Changeable During Run Yes MON 2 Terminal Meter Adjustment Program Terminal Analog Output Terminals This parameter is used to set the gain of the MON2 output terminal and is used...

Page 198: ... terminal i e voltage or current The output voltage and current range is 0 10 VDC and 0 20 mA respectively See F005 for additional information on this parameter Settings 0 0 10 V 1 0 20 mA Direct Access Number F681 Parameter Type Selection List Factory Default 0 10V Changeable During Run No FM Output Gradient Characteristic Program Terminal Analog Output Terminals This parameter sets the output re...

Page 199: ...AM output terminal The AM output terminal response may be set to respond inversely or directly to the input signal See F670 for additional information on this parameter Settings 0 Minus Negative Gradient 1 Plus Positive Gradient Direct Access Number F685 Parameter Type Selection List Factory Default Plus Changeable During Run Yes AM Bias Adjustment Program Terminal Analog Output Terminals This par...

Page 200: ...eter is used to set the output signal type of the MON2 output terminal See F674 for additional information on this parameter Settings 0 10 V 10 V 1 0 10 V 2 0 20 mA Direct Access Number F691 Parameter Type Selection List Factory Default 0 10V Changeable During Run No MON 2 Output Gradient Characteristic Program Terminal Analog Output Terminals This parameter sets the output response polarity of th...

Page 201: ...oad in process units i e units time Example An output frequency of 100 Hz would be displayed as 50 Hz if using a multiplier of 0 5 for this parameter Note PID frequency limiting parameters are not affected by this setting i e F364 F365 F367 and F368 Direct Access Number F702 Parameter Type Numerical Factory Default 0 00 OFF Changeable During Run Yes Minimum 0 00 Maximum 200 00 Free Unit Program Ut...

Page 202: ...m Maximum Freq F011 Units Hz Change Step Selection 1 Program Utilities Display Parameters In conjunction with the parameter setting of F708 this parameter sets the amount that the output speed will increase or decrease for each speed command change entered from the EOI using the Rotary Encoder Direct Access Number F707 Parameter Type Numerical Factory Default 0 00 Changeable During Run Yes Minimum...

Page 203: ...al Operation Panel Parameters While operating using the LED Keypad Option this parameter Enables Disables the ability to change the frequency command value Settings 0 Unlocked 1 Locked Direct Access Number F730 Parameter Type Selection List Factory Default Unlocked Changeable During Run Yes Panel Cable Breakage Detection Direct Access Number F731 Program Special Operation Panel Parameters Paramete...

Page 204: ...ist Factory Default Locked Changeable During Run Yes Panel Keys Operation Program Special Operation Panel Parameters This parameter Enables Disables EOI keypad operation Select Locked to disable all keypad entries Cycle the power to the ASD to activate the changes made to this parameter To unlock the EOI keypad for normal operation press and hold the Rotary Encoder for greater than 5 seconds This ...

Page 205: ...ttings 0 None Disabled 1 At Trip 2 At Trigger Direct Access Number F740 Parameter Type Selection List Factory Default At Trip Changeable During Run Yes Trace Cycle Program Utilities Trace This parameter sets the record time for the Trace Data events selected at F742 F745 See F740 for additional information on this parameter Settings 0 4 mS 1 20 mS 2 100 mS 3 1 Second 4 10 Seconds Direct Access Num...

Page 206: ...gram Utilities Display Parameters This parameter is used to set the disposition of the kWh meter reading at power off Settings 0 Disabled 1 Enabled Direct Access Number F748 Parameter Type Selection List Factory Default Enabled Changeable During Run Yes Integral Output Power Display Unit Direct Access Number F749 Program Utilities Display Parameters Parameter Type Selection List This parameter set...

Page 207: ...actory Default 00 This parameter operates in conjunction with parameter F784 This parameter is used to configure the MAC Address 4 section of the MAC address of the device See F784 for additional information on this parameter Changeable During Run Yes Minimum 00 Maximum 255 MAC Address 5 Direct Access Number F788 Program Communications Ethernet Settings Parameter Type Numerical Factory Default 00 ...

Page 208: ... 3 Direct Access Number F794 Program Communications Ethernet Settings Parameter Type Numerical Factory Default 0000 See F792 for information on this parameter Changeable During Run Yes Minimum 0000 Maximum FFFF Device Name Data 4 Direct Access Number F795 Program Communications Ethernet Settings Parameter Type Numerical Factory Default 0000 See F792 for information on this parameter Changeable Dur...

Page 209: ...fault 0000 See F792 for information on this parameter Changeable During Run Yes Minimum 0000 Maximum FFFF Baud Rate 2 Wire RS485 Program Communications Communication Settings This parameter plays a role in the setup of the communications network by establishing the Baud Rate of the communications link The communications network includes other ASDs and Host Control computers that monitor the status...

Page 210: ...SDs and Host Control computers that monitor the status of the ASD s transfers commands and loads or modifies the parameter settings of the ASD Changes made to this parameter require that the power be cycled off then on for the changes to take effect Direct Access Number F802 Parameter Type Numerical Factory Default 0 Changeable During Run Yes Minimum 0 Maximum 247 Communications Time Out 2 and 4 w...

Page 211: ...nges to take effect Settings Settings Are For 2 Wire 4 Wire 0 No Action No Action 1 Alarm No Action 2 Trip No Action 3 No Action Alarm 4 Alarm Alarm 5 Trip Alarm 6 No Action Trip 7 Alarm Trip 8 Trip Trip Direct Access Number F804 Parameter Type Selection List Factory Default Trip Trip Changeable During Run Yes Send Delay Time 2 Wire RS485 Program Communications Communication Settings This paramete...

Page 212: ... Stop If Error Detected 1 Follower Continues Operation If Error Detected 2 Follower Emergency Off If Error Detected 3 Master Frequency Command 4 Master Output Frequency 5 Master Torque Reference 6 Master Output Torque Direct Access Number F806 Parameter Type Selection List Factory Default Follower Decel Stop Changeable During Run Yes Communication Protocol 2 Wire RS485 Direct Access Number F807 Pr...

Page 213: ...he Speed Control mode and using one of the control sources from Settings above the settings that determine the gain and bias properties of the input signal are Communications Reference Speed Setpoint 1 frequency F812 the communications input signal value that represents Communications Reference Speed Setpoint 1 frequency F811 Communications Reference Speed Setpoint 2 frequency F814 and the communi...

Page 214: ...on for the changes to take effect Direct Access Number F813 Parameter Type Numerical Factory Default 100 Changeable During Run Yes Minimum 0 Maximum 100 Units Point 2 Frequency Program Communications Communication Adjustments This parameter is used to set the gain and bias of the Communications Reference speed control input See F811 for additional information on this parameter This parameter sets ...

Page 215: ...s used to assign the command station Changeable During Run Yes Minimum 0 Maximum 64 Baud Rate 4 Wire RS485 Program Communications Communication Settings This parameter sets the RS485 baud rate Changes made to this parameter require that the power be cycled off then on for the changes to take effect Settings 0 9600 bps 1 19200 bps 2 38400 bps Direct Access Number F820 Parameter Type Selection List ...

Page 216: ... Parameter Type Selection List Factory Default Automatic Detection This parameter establishes the baud rate detection setting of the left port Settings 0 Automatic Detection 1 10Mbps Full 2 10Mbps Half 3 100Mbps Full 4 100Mbps Half Changeable During Run Yes RS485 Send Delay Time 4 Wire RS485 Program Communications Communication Settings This parameter sets the RS485 response delay time Changes mad...

Page 217: ...D the ASD response if an error is incurred is set here Note Select a Follower function here if F806 is configured as a Master Output controller for any other ASD in the system Otherwise an EOI failure will result Changes made to this parameter require that the power be cycled off then on for the changes to take effect Settings 0 Follower Decel Stop if Error Detected 1 Follower Continues Operation ...

Page 218: ...mmunication Settings This parameter sets the communications protocol for ASD to ASD communications Settings 0 Toshiba 1 Modbus 2 BACnet Direct Access Number F829 Parameter Type Selection List Factory Default Toshiba Changeable During Run Yes Communication Option DeviceNet Profibus Setting 1 Program Communications Communication Options While using the DeviceNet Profibus communications protocol this...

Page 219: ...ommunication Option DeviceNet Profibus Setting 5 Program Communications Communication Options See F831 for information on this parameter Direct Access Number F834 Parameter Type Selection List Factory Default 0000h Changeable During Run Yes Communication Option DeviceNet Profibus Setting 6 Program Communications Communication Options See F831 for information on this parameter Direct Access Number ...

Page 220: ... Communication Option DeviceNet Profibus Setting 13 Program Communications Communication Options See F841 for information on this parameter Direct Access Number F844 Parameter Type Selection List Factory Default 0000h Changeable During Run Yes Communication Option DeviceNet Profibus Setting 14 Program Communications Communication Options See F841 for information on this parameter Direct Access Num...

Page 221: ...on 1 Do Nothing Continue Programmed Operation 2 Deceleration Stop 3 Coast Stop 4 Emergency Off 5 Preset Speed Setting of F852 Direct Access Number F851 Parameter Type Selection List Factory Default Stop and Terminate Communication Changeable During Run Yes Preset Speed Operation Program Communications Communication Options This parameter setting is used to set the Preset Speed selection to be used...

Page 222: ...ng Program Communications Communication Settings This parameter plays a role in the setup of the communications network by establishing the targets of a Reset command received via the communications link Settings 0 1 Reset Option Board and ASD Direct Access Number F899 Parameter Type Selection List Factory Default Changeable During Run No Input Function Target 1 Program My Function My Function Uni...

Page 223: ...le During Run No Input Function Target 3 Program My Function My Function Unit 1 This parameter plays a role in the setup of the My Function feature by selecting the functionality of the programmable Input Function Target 3 terminal This setting assigns the function of the programmable Input Function Target 3 terminal to any one of the user selectable functions listed in Table 12 on pg 238 Table 13...

Page 224: ... terminal This setting assigns the function of the programmable Input Function Target 2 terminal to any one of the user selectable functions listed in Table 12 on pg 238 Table 13 on pg 239 or Table 15 on pg 242 See F977 for additional information on this parameter Direct Access Number F908 Parameter Type Selection List Factory Default 0 Disabled Changeable During Run No Input Function Command 2 Pr...

Page 225: ...to assign a user selected logical operator to two user selected Input Function Target variables enable a counter timer function or perform a hold reset function Table 16 on pg 244 lists the available selections Their use and selection requirements are described in an example at F977 Direct Access Number F913 Parameter Type Selection List Factory Default 0 NOP Changeable During Run No Input Functio...

Page 226: ... and F977 for additional information on this parameter Direct Access Number F917 Parameter Type Selection List Factory Default 0 Disabled Changeable During Run No My Function Percent Data 1 Program My Function My Function Data This parameter is used to set the trigger threshold level of the analog signal of the My Function Percent Data 1 The analog signal is selected using the Input Setting number...

Page 227: ... Changeable During Run Yes Minimum 0 00 Maximum 200 00 Units My Function Frequency Data 1 Program My Function My Function Data This parameter is used to set the trigger threshold level of the analog signal of the My Function Frequency Data 1 The analog signal is selected using the Input Setting number from Table 13 on pg 239 Direct Access Number F923 Parameter Type Numerical Factory Default 0 00 C...

Page 228: ...crete terminal input activation that does not equal or exceed this setting will be ignored Direct Access Number F928 Parameter Type Numerical Factory Default 0 01 Changeable During Run Yes Minimum 0 01 Maximum 600 00 Units Seconds My Function Time Data 2 Program My Function My Function Data This parameter is used to set the response delay of the My Function Time Data 2 terminal The applied discret...

Page 229: ...eter is used to set the pulse count threshold value used to trigger the discrete output COUNT1 ON Timer COUNT1 ON Timer outputs a 1 upon reaching the threshold setting of this parameter Direct Access Number F933 Parameter Type Numerical Factory Default 0 Changeable During Run Yes Minimum 0 Maximum 9999 Units Pulses My Function Count Data 2 Program My Function My Function Data This parameter is use...

Page 230: ...rform a hold reset function Table 16 on pg 244 lists the available selections Their use and selection requirements are described in an example at F977 Direct Access Number F938 Parameter Type Selection List Factory Default 0 NOP Changeable During Run Yes Input Function Target 3 Program My Function My Function Unit 4 This parameter plays a role in the setup of the My Function feature by selecting t...

Page 231: ...terminal This setting assigns the function of the programmable Input Function Target 2 terminal to any one of the user selectable functions listed in Table 12 on pg 238 Table 13 on pg 239 or Table 15 on pg 242 See F977 for additional information on this parameter Direct Access Number F943 Parameter Type Selection List Factory Default 0 Disabled Changeable During Run Yes Input Function Command 2 Pr...

Page 232: ...to assign a user selected logical operator to two user selected Input Function Target variables enable a counter timer function or perform a hold reset function Table 16 on pg 244 lists the available selections Their use and selection requirements are described in an example at F977 Direct Access Number F948 Parameter Type Selection List Factory Default 0 NOP Changeable During Run Yes Input Functi...

Page 233: ...additional information on this parameter Direct Access Number F952 Parameter Type Selection List Factory Default 0 Disabled Changeable During Run Yes Input Function Target 1 Program My Function My Function Unit 7 This parameter plays a role in the setup of the My Function feature by selecting the functionality of the programmable Input Function Target 1 terminal This setting assigns the function o...

Page 234: ...e During Run Yes Input Function Target 3 Program My Function My Function Unit 7 This parameter plays a role in the setup of the My Function feature by selecting the functionality of the programmable Input Function Target 3 terminal This setting assigns the function of the programmable Input Function Target 3 terminal to any one of the user selectable functions listed in Table 12 on pg 238 Table 13...

Page 235: ...Function Analog This parameter plays a role in the setup of the My Function feature by selecting the functionality to which the adjustment of F959 is applied Settings 0 Disabled None 1 Acceleration Rate 2 Upper Limit Frequency 3 Acceleration Multiplication Factor 4 Deceleration Multiplication Factor 5 Manual Torque Boost 6 Over Current Stall F601 7 Thermal Protection 8 Speed Loop Proportional Gain...

Page 236: ...hermal Protection 8 Speed Loop Proportional Gain F460 9 Drooping Gain F320 10 PID Proportional Gain F362 See the My Function Instruction Manual P N E6581335 for a complete description of the setup requirements and operational information of the Analog Function Assigned Object parameter Direct Access Number F964 Parameter Type Selection List Factory Default 0 Disabled Changeable During Run No Monit...

Page 237: ...he Monitor Display Input Setting number from Table 15 on pg 242 to output the corresponding function Use the Communication Number if operating using communications See the My Function Instruction Manual P N E6581335 for a complete description of the setup requirements and operational information of the Monitor Output Function parameter Direct Access Number F967 Parameter Type Selection List Factor...

Page 238: ...eter F969 selection to be recorded and output as a monitored function See the My Function Instruction Manual P N E6581335 for a complete description of the setup requirements and operational information of the Monitor Output Function parameter Settings 0 Normal 1 Maximum 2 Minimum Direct Access Number F970 Parameter Type Selection List Factory Default Normal Changeable During Run Yes Monitor Outpu...

Page 239: ...hangeable During Run No Virtual Input Terminal Selection 2 Program Terminal Input Terminals This parameter is used to set the functionality of the Virtual Input Terminal 2 As a virtual terminal it exists only in memory and is considered always to be in its True connected to CC state It is often practical to assign a function to this terminal that the user desires to be maintained regardless of ext...

Page 240: ...o assign a function to this terminal that the user desires to be maintained regardless of external conditions or operations This parameter sets the programmable Virtual Input Terminal 4 terminal to one of the functions that are listed in Table 10 on pg 234 In addition the input terminal must be specified as Normally Open or Normally Closed Direct Access Number F976 Parameter Type Selection List Fa...

Page 241: ... Function Target 1 to 5 F900 This setting assigns S1 as the control input terminal 5 Set Output Function Assigned to 21 F905 This setting is a command that writes the F115 selection S1 to Virtual Input Terminal 1 activating both 6 Enable the My Function parameter at F977 by selecting My Function Always On or selecting My Function With TB Signal If set to My Function Always On the combination of ST...

Page 242: ...e listing of available settings 5 Set Input Function Target 2 F902 to 1026 Low Current Alarm See Table 13 on pg 239 for a complete listing of available settings 6 Set Input Function Command 1 F901 to AND 3 This setting assigns an operator to the Input Function Target 1 and the Input Function Target 2 settings 7 Set Output Function Assigned F905 to 1222 This setting will transfer the results of the...

Page 243: ... 23 DC Braking The ASD outputs a DC current that is injected into the windings of the motor to quickly brake the motor 24 25 ACC DEC Switching Activating discrete input terminal Accel Decel Switching allows for the selection of Accel Decel profiles 1 2 as shown below See F504 for additional information on this terminal setting 28 29 V f Switching Signal Activating discrete input terminal V f Switc...

Page 244: ...it setting or increases the speed of the motor in steps See F264 for additional information on this feature 90 91 UP DOWN Frequency down Decreases the speed of the motor for the duration of activation until reaching the Lower Limit setting or decreases the speed of the motor in steps See F264 for additional information on this feature 92 93 UP DOWN Frequency clear While operating in the Up Down Fr...

Page 245: ... terminal is not active 144 145 TBA ON Float Activation runs the ASD at the setting of F390 146 147 TBA OFF Float Activation has a dual function 1 Changes the operating mode from Process Hold to Direct 2 Turns off the ASD 148 149 TBA Trigger Float Activation changes the operating mode from Process Hold to Direct 150 151 TBA Warning Float This input is typically connected to a float switch that whe...

Page 246: ...ion Monitor 4 With Sign 11 Torque Current 50 Signed Output Frequency 12 Excitation Current 51 Signed Frequency Command pre PI 13 PID Feedback Value 52 Signed Compensated Frequency 14 Motor Overload Ratio 53 Signed Speed Feedback Real Time 15 ASD Overload Ratio 54 Signed Speed Feedback 1 Sec Filter 16 DBR Overload Ratio not used 55 Signed Torque 17 DBR Load Ratio not used 56 Signed Torque Command 1...

Page 247: ...tandby 20 B15 4 Reset 21 Virtual Input Terminal 1 5 S1 22 Virtual Input Terminal 2 6 S2 23 Virtual Input Terminal 3 7 S3 24 Virtual Input Terminal 4 8 S4 25 Internal Terminal 1 9 LI1 26 Internal Terminal 2 10 LI2 27 Internal Terminal 3 11 LI3 28 Internal Terminal 4 12 LI4 29 Internal Terminal 5 13 LI5 30 Internal Terminal 6 14 LI6 31 Internal Terminal 7 15 LI7 32 Internal Terminal 8 16 LI8 Buy www...

Page 248: ...40 Run Stop 1136 136 External Device 1 1042 42 Serious Failure OCA OCL EF Phase Failure 1138 138 External Device 2 1044 44 Light Failure OL OC1 2 3 or OP 1140 140 External Device 3 1046 46 Commercial Power ASD Switching Output 1 1142 142 External Device 4 1048 48 Commercial Power ASD Switching Output 2 1144 144 External Device 5 1050 50 Cooling Fan On Off 1146 146 External Device 6 1052 52 Jogging...

Page 249: ...250 250 My Function Output 15 1240 240 My Function Output 10 1252 252 My Function Output 16 1242 242 My Function Output 11 1254 254 Always Off 1244 244 My Function Output 12 Table 13 Output Terminal Assignments My Function Input Setting Assignments and Parameter Input Setting Numbers for the FLA B C O1A O1B OUT1 O2A O2B OUT2 OUT3 OUT6 and R1 R4 Continued Discrete Output Terminal Assignment Selecti...

Page 250: ...oad Ratio 0 01 16 FD25 DBR Overload Ratio not used 1 17 FD28 DBR Load Ratio not used 1 18 FD29 Input Power 0 01 kW 19 FD30 Output Power 0 01 kW 23 FE39 V I Option AI2 1 24 FE35 RR Input 0 01 25 FE36 V I Input 0 01 26 FE37 RX Input 0 01 27 FE38 RX2 Input 1 28 FE40 FM Output 0 01 29 FE41 AM Output 0 01 30 FE51 Signed 100 Meter Adjust Value 1 31 FA51 Communication Data N A 32 FE50 Signed 185 Meter Ad...

Page 251: ...FE22 PID Feedback Value 0 01 Hz 2023 FD23 3023 FE23 Motor Overload Ratio 0 01 2024 FD24 3024 FE24 ASD Overload Ratio 0 01 2025 FD25 3025 FE25 DBR Overload Ratio not used 1 2028 FD28 3028 FE28 DBR Load Ratio not used 1 2029 FD29 3029 FE29 Input Power 0 01 kW 2030 FD30 3030 FE30 Output Power 0 01 kW 3031 FE31 Pattern Operation Group Number 0 1 3032 FE32 Pattern Operation Cycles Remaining 1 3033 FE33...

Page 252: ... Expansion I O Card 2 CPU Version 3076 FE76 Integral Input Power 0 01 kW 3077 FE77 Integral Output Power 0 01 kW 3084 FE84 16 Bit BIN BCD Input Value 1 Note 1 If no PG feedback is used an estimated speed value is displayed Note 2 My Function cannot process negative values A negative value is processed by My Function as an absolute value Table 15 Input Function Target Selections and the Associated ...

Page 253: ... if A B 0 if A B 11 LT Compares data Outputs 1 if A B 0 if A B 12 LE Compares data Outputs 1 if A B 0 if A B 13 ASUB Outputs absolute difference between A and B A B 14 FB_ON_DELAY Timer Enables the On response time delay settings of My Function Time Data 1 5 F928 F932 for My Function Data 15 FB_OFF_DELAY Timer Enables the Off response time delay settings of My Function Time Data 1 5 F928 F932 for ...

Page 254: ...D Faults and a Trip is incurred Fault and Trip are sometimes used interchangeably A Trip is a safety feature the result of a Fault that disables the Q9 Plus ASD system and removes the 3 phase power from the motor in the event that a subsystem of the ASD is malfunctioning or if one or more of the variables listed below exceeds its normal range in time and or magnitude Current Voltage Speed Temperat...

Page 255: ...n of the activation Table 17 User Notification Codes LED Screen LCD Screen Description Atn Autotune Active Autotune function is active nErr No Error No active errors LOFr Virtual Linear Pump Low Frequency Virtual Linear Pump function is operating at the Low Frequency Limit setting Pump Virtual Linear Pump On Virtual Linear Pump function is enabled and active Buy www ValinOnline com Phone 844 385 3...

Page 256: ...he malfunction cannot be determined contact the TIC Customer Support Center for further information on the condition and for an appropriate course of action In the event that multiple alarms are activated only the first to be detected will be displayed Table 18 Alarms LED Screen LCD Screen Alarm Description Possible Cause 4 20 mA 4 20 mA 4 20 Signal Loss Misconnection poor connection or broken wir...

Page 257: ... EOI E OFF command was received remotely HLD Heavy Load Motor ASD Over Loaded Acceleration time is too short ASD is improperly matched to the application Excessive load LLD Light Load Light Load ASD is improperly matched to the application LLT Lower Limit Lower Limit Time Parameter F256 adjustment is required MOFF Main Under Volts Under Voltage Main Circuit Power Supply 3 phase input voltage low D...

Page 258: ...ating ASD is operating at an elevated temperature ASD is too close to heat generating equipment Cooling fan vent is obstructed Cooling fan is inoperative Internal thermistor is disconnected OT Over Torque Torque Requirement in Excess of the Setting of F616 or F617 for a Time Longer than the Setting of F618 ASD is improperly matched to the application Parameter F616 or F617 setting is too low Obstr...

Page 259: ... Current of the ASD is Below the Level Defined at F611 Disable detection at F610 Parameter F611 adjustment is required Table 18 Alarms Continued LED Screen LCD Screen Alarm Description Possible Cause Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 260: ... OL1 ASD Overload ASD Overload Acceleration time is too short DC Injection current is too high V f setting needs to be adjusted Motor is running during restart ASD motor is improperly matched to the application ERR2 ASD RAM Fault ASD RAM Fault Service call is required ERR3 ASD ROM Fault ASD ROM Fault Service call is required ETYP ASD Type Error ASD Type Error Firmware information typeform loaded i...

Page 261: ...orque Boost Err Autotuning Error Torque Boost Error Improper setting at F410 E Emergency Off Emergency Off Command Received Via Keypad or Remotely Output Signal From the ASD is Terminated Stop Reset was pressed twice at the EOI E Off command was received remotely Select stopped method at F603 E 12 Encoder Loss Encoder Loss Encoder signal is not received ERR6 Gate Array Fault Gate Array Fault Defec...

Page 262: ... to the application Phase to phase short U T1 V T2 or W T3 Acceleration time is too short Voltage Boost setting is too high Motor machine is jammed Mechanical brake is engaged while the ASD is running Short Circuit Detection adjustment is required F613 ASD current exceeds 320 or 340 of the rated FLA on ASDs that are greater than 100 HP or that are 100 HP or less respectively during acceleration No...

Page 263: ...cal brake is engaged while the ASD is running ASD current exceeds 320 or 340 of the rated FLA on ASDs that are greater than 100 HP or that are 100 HP or less respectively during acceleration OC3 OC3P Over Current Run Over Current During Fixed Speed Operation ASD Motor is improperly matched to the application Load fluctuations ASD is operating at an elevated temperature ASD current exceeds 320 or 3...

Page 264: ...un Over Voltage During Fixed Speed Operation Load fluctuations 3 phase input voltage out of specification E 21 Stack Err Stack Overflow Error Service call is required SOUT Step Out PM Step Out For PM Motors Only Service call is required OCA1 U Phase OC U Phase Over Current Low impedance at the U T1 phase OCA2 V Phase OC V Phase Over Current Low impedance at the V T2 phase OCA3 W Phase OC W Phase O...

Page 265: ... Recorded Parameters parameter readings at the time that the trip occurred Table 20 Trip History Record Parameters Clearing a Trip Once the cause of the trip has been corrected performing a Reset re enables the Q9 Plus ASD for normal operation The record of a trip may also be cleared using one of the following methods Cycling power trip info may be saved via F602 if desired Pressing the Stop Reset...

Page 266: ...ention to identify the ASD typeform and for placing orders Q9 Plus Part Numbering Convention Note The Type 1 enclosed versions of these drives meet or exceed the specification UL 50 1995 the Standard for Heating and Cooling Equipment and complies with the applicable requirements for installation in a compartment handling conditioned air Note All Toshiba ASD enclosures carry an IP20 rating Buy www ...

Page 267: ... 8 7 220 4 5 114 N A 0 098 2 5 0 217 5 5 2 2025 3 3 2035 6 1 155 11 1 281 6 5 164 9 8 249 5 4 138 5 2055 4 7 5 2080 6 9 175 12 6 320 11 1 283 6 2 158 0 236 6 0 5A 10 2110 8 3 210 7 6 194 7 5 190 0 118 3 0 0 276 7 0 5B 15 2160 9 1 230 16 7 425 7 5 191 15 2 386 8 3 210 20 2220 6 25 2270 Figure 39 9 4 240 16 5 420 8 3 212 15 9 403 8 1 206 0 295 7 5 30 2330 7B 40 2400 12 6 320 21 7 550 9 5 242 20 7 52...

Page 268: ...5 9 403 8 1 206 0 295 7 5 7A 50 4500 Figure 40 21 7 550 9 5 242 20 8 529 60 4600 8 75 4750 12 6 320 24 8 630 11 4 290 23 8 605 11 0 280 0 177 4 5 0 394 10 100 410K 125 412K 9 150 415K Figure 41 12 2 310 26 8 680 14 6 370 25 6 650 9 8 250 0 224 5 7 0 472 12 10 200 420K 13 0 350 30 8 782 29 8 758 11 7 298 11 250 425K 13 8 334 37 4 950 36 2 920 11 2 285 12 300 430K 16 9 430 13 8 350 350 435K 13 400 4...

Page 269: ...260 Q9 Plus ASD Installation and Operation Manual Figure 38 See Table 21 and 22 for Actual Dimensions Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 270: ...Q9 Plus ASD Installation and Operation Manual 261 Figure 39 See Table 21 and 22 for Actual Dimensions Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 271: ...262 Q9 Plus ASD Installation and Operation Manual Figure 40 See Table 21 and 22 for Actual Dimensions Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 272: ...Q9 Plus ASD Installation and Operation Manual 263 Figure 41 See Table 21 and 22 for Actual Dimensions Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 273: ...put Voltage 3 Ph 50 60 2 Hz Output Voltage 3 Ph Variable Frequency Typical Motor HP 2015 4 8 A 5 3 A 200 240VAC 10 Input Voltage Level Max 1 0 2025 7 8 A 8 6 A 2 0 2035 11 0 A 12 1 A 3 0 2055 17 5A 19 3 A 5 0 2080 25 3 A 27 8 A 7 5 2110 32 2 A 35 4 A 10 2160 48 3 A 53 1 A 15 2220 62 1 A 68 3 A 20 2270 78 2 A 86 0 A 25 2330 92 0 A 101 A 30 2400 120 A 132 A 40 Buy www ValinOnline com Phone 844 385 3...

Page 274: ...vel Max 1 0 4025 3 4 A 3 7 A 2 0 4035 4 8 A 5 3 A 3 0 4055 7 6 A 8 4 A 5 0 4080 11 0 A 12 1 A 7 5 4110 14 0 A 15 4 A 10 4160 21 0 A 23 1 A 15 4220 27 0 A 29 7 A 20 4270 34 0 A 37 4 A 25 4330 40 0 A 44 0 A 30 4400 52 0 A 57 2 A 40 4500 65 0 A 71 5 A 50 4600 77 0 A 84 7 A 60 4750 96 0 A 106 A 75 410K 124 A 136 A 100 412K 156 A 172 A 125 415K 180 A 198 A 150 420K 240 A 264 A 200 425K 302 A 332 A 250 ...

Page 275: ... used with the Q9 Plus ASD Note Cable Terminal specifications are based on the rated current of the Q9 Plus ASD and Do Not include the 10 Service Factor Note Use only 75 C copper wire cable for motor and power connections Table 25 230 Volt Q9 Plus ASD Cable Terminal Torque Specifications Model Number VT130Q9 Wire Cable Size Lug Size Range Terminal Board Wire Size Torque AWG or kcmil Input Output P...

Page 276: ...e Size Lug Capacity for Input Output Power In Lbs N m Recommended Maximum 3Ø Input 3Ø Output TB1 4 Terminals 3Ø Input 3Ø Output 4015 14 10 14 to 10 20 3 core shield Torque to 5 3 0 6 12 4 1 4 4025 14 10 4035 14 10 4055 14 10 4080 14 10 4110 12 8 12 to 8 26 6 3 4160 8 4 10 to 4 4220 8 4 4270 6 3 8 to 2 47 8 5 4 4330 6 3 4400 6 2 4 to 1 0 212 24 4500 4 2 4600 3 2 4750 1 4 0 2 to 300 360 41 410K 1 0 ...

Page 277: ...30 92 0 HLL36100 2400 40 120 HLL36125 4015 1 0 2 1 Contact TIC Customer Service 4025 2 0 3 4 Contact TIC Customer Service 4035 3 0 4 8 Contact TIC Customer Service 4055 5 0 7 6 HLL36025 4080 7 5 11 HLL36040 4110 10 14 HLL36050 4160 15 21 HLL36070 4220 20 27 HLL36090 4270 25 34 HLL36100 4330 30 40 HLL36100 4400 40 52 HLL36125 4500 50 65 HLL36150 4600 60 77 JLL36200 4750 75 96 JLL36225 410K 100 124 ...

Page 278: ... 227 Analog Output Terminals 48 Annual Average Ambient Temperature 181 ASD Characteristics 11 ASD Load 43 ASD Number 201 ASD OL Overload Real 43 ASD OL Overload Trip 43 ASD Operation at Disconnect 212 ASD Overload 181 ASD Side Switching Delay 143 ASD Motor Connection Diagram 16 ASD to ASD Communications 2 Wire 203 ASD to ASD Communications 4 wire 208 At Trip Recorded Parameters 256 Auto Mode 28 Au...

Page 279: ...rtional Gain 160 Current Voltage Specifications 264 D DBR Load 44 DBR OL Overload Real 43 DBR OL Overload Trip 44 DC Bus Voltage 43 DC Injection Braking 54 DC Injection Braking Current 125 DC Injection Braking Start Frequency 125 DC Injection Braking Time 126 Deceleration Time 1 86 Deceleration Time 2 168 Default Setting Changes 35 Direct Access 51 Direction 45 Disconnection Detection Extended Tim...

Page 280: ...223 224 Input Function Command 2 214 215 216 221 222 223 225 Input Function Target 1 213 215 216 220 222 223 224 Input Function Target 2 214 215 216 221 222 223 225 Input Function Target 3 214 215 217 221 222 224 225 Input Power 44 Input Special Functions 49 Input Terminal 1 F Function 94 Input Terminal 1 F Response Time 101 Input Terminal 10 LI2 Function 96 Input Terminal 11 LI3 Function 96 Input...

Page 281: ...tion 31 229 Monitor Output Function 41 229 Monitor Output Function Command 11 228 Monitor Output Function Command 21 228 Monitor Output Function Command 31 229 Monitor Output Function Command 41 230 Monitor Screen 30 Motor Braking 11 Motor Capacity 70 Motor Characteristics 10 Motor Connection Diagram 16 Motor Constant 1 Torque Boost 155 Motor Constant 2 No Load Current 155 Motor Constant 3 Leak In...

Page 282: ...ion Hysteresis 178 Over Torque Detection Level During Power Running 178 Over Torque Detection Level During Regenerative Braking 178 Over Torque Detection Time 178 Over Torque Parameters 55 Over Torque Trip 178 Over Voltage Limit Operation 137 Over Voltage Limit Operation Level 180 P P24 20 22 P24 Output 24 PA 15 Panel Emergency Off Lockout 194 Panel Frequency Lockout 194 Panel Keys Operation 195 P...

Page 283: ... Regenerative Braking Torque Limit 1 Level 159 Regenerative Power Ridethrough Control Level 180 Regenerative Power Ridethrough Mode 135 RES 20 21 Reset 52 85 Retain Trip Record at Power Down 175 Retry Selection 136 Retry Restart 55 Ridethrough Time 138 Root Menu Items 41 Rotary Encoder 28 RR 20 21 RR Input 24 44 RR Input Bias 162 RR Input Gain 162 RR Input Point 1 Frequency 113 RR Input Point 1 Ra...

Page 284: ...arning Float 236 Terminal 48 Terminal Board 13 20 23 Terminal Descriptions 21 Time Limit For Lower Limit Frequency Operation 126 Time Based Alternation 154 157 Time Based Alternation Direct Mode Emergency Setpoint 160 Time Based Alternation Direct Mode Response Time 158 Time Based Alternation Emergency Timer 154 Time Based Alternation Period 157 Time Based Alternation Process Hold Mode Response Ti...

Page 285: ... Selection 1 230 Virtual Input Terminal Selection 2 230 Virtual Input Terminal Selection 3 230 Virtual Input Terminal Selection 4 231 Virtual Linear Pump 46 Virtual Linear Pump Application Operating Mode 148 Virtual Linear Pump Application Type 150 Virtual Linear Pump Auto Start Stop Delay Timer 149 Virtual Linear Pump Auto Start Stop Mode 149 Virtual Linear Pump Command Source 151 Virtual Linear ...

Reviews: