Q9 Plus ASD Installation and Operation Manual
239
Table 13. Output Terminal Assignments,
My Function Input Setting
Assignments, and Parameter/Input Setting
Numbers for the
FLA
/
B
/
C
,
O1A
/
O1B
(OUT1),
O2A
/
O2B
(OUT2),
OUT3
–
OUT6
, and
R1
–
R4
.
Discrete Output Terminal Assignment Selections
Input
Setting
Param.
Setting
Function
Input
Setting
Param.
Setting
Function
1000
0
Lower-Limit Frequency
1096
96
Specified Data Output 3
1002
2
Upper-Limit Frequency
1098
98
Specified Data Output 4
1004
4
Low-Speed Signal
1100
100
Specified Data Output 5
1006
6
Acceleration/Deceleration Completion
1102
102
Specified Data Output 6
1008
8
Speed Reach Signal
1104
104
Specified Data Output 7
1010
10
Failure FL (All Trips)
1106
106
Light Load Detected
1012
12
Failure FL (Except EF, OCL, EPHO, and OL2)
1108
108
Heavy Load Detected
1014
14
Over-Current (OC) Alarm
1110
110
Positive Torque Limit
1016
16
ASD Overload (OL1) Alarm
1112
112
Negative Torque Limit
1018
18
Motor Overload (OL2) Alarm
1114
114
External Rush Suppression Relay Activated
1020
20
Over-Heat Alarm
1118
118
Completion of Stop Positioning
1022
22
Over-Voltage Alarm
1120
120
L-STOP
1024
24
Main Circuit (MOFF) Under-Voltage Alarm
1122
122
Power Failure Synchronized Operation
1026
26
Low-Current Alarm
1124
124
Traverse in Progress
1028
28
Over-Torque Alarm
1126
126
Traverse Deceleration Active
1030
30
DBR Overload Alarm (not used)
1128
128
Part Replacement Alarm
1032
32
Emergency Off Active
1130
130
Over-Torque Alarm
1034
34
Retry Active
1132
132
Frequency Command ½ Selection
1038
38
PID Deviation Limit
1134
134
Failure FL (Except Emergency Off)
1040
40
Run/Stop
1136
136
External Device 1
1042
42
Serious Failure (OCA, OCL, EF, Phase Failure)
1138
138
External Device 2
1044
44
Light Failure (OL, OC1, 2, 3, or OP)
1140
140
External Device 3
1046
46
Commercial Power/ASD Switching Output 1
1142
142
External Device 4
1048
48
Commercial Power/ASD Switching Output 2
1144
144
External Device 5
1050
50
Cooling Fan On/Off
1146
146
External Device 6
1052
52
Jogging Operation Active (Jog Run Active)
1148
148
Sealing Water
1054
54
Panel/Terminal Board Operation Switching
1150
150
NPSH/No Flow Alarm
1056
56
Cumulative Run-Time Alarm
1154
154
TBA Active
1058
58
ProfiBus/DeviceNet/CC-Link Communication Error
1156
156
TBA Alarm Float
1060
60
Forward/Reverse Switching
1158
158
Local/Remote (Hand/Auto) Switching
1062
62
Ready for Operation 1
1160
160
Forced Operation (RUN)
1064
64
Ready for Operation 2
1162
162
Forced Operation (Firespeed)
1066
66
POFF Alarm
1164
164
Under-Torque Detection
1070
70
Alarm Status Active
1166
166
Frequency Command From (RR/S4)
1072
72
Forward Speed Limit
1168
168
Frequency Command From (V/I)
1074
74
Reverse Speed Limit
1170
170
Frequency Command From (RX)
1076
76
ASD Healthy Output
1172
172
PTC Alarm Detection
1078
78
RS485 Communication Error
1174
174
Power Removal Signal
1080
80
Error Code Output 1
1176
176
V/I Input Wire Breakage
1082
82
Error Code Output 2
1178
178
Damper Command
1084
84
Error Code Output 3
1222
222
My Function Output 1
1086
86
Error Code Output 4
1224
224
My Function Output 2
1088
88
Error Code Output 5
1226
226
My Function Output 3
1090
90
Error Code Output 6
1228
228
My Function Output 4
1092
92
Specified Data Output 1
1230
230
My Function Output 5
1094
94
Specified Data Output 2
1232
232
My Function Output 6