244
Q9 Plus ASD Installation and Operation Manual
Table 16. My Function Operator Selections.
My Function Computational Selections
Input
Function
Command
Function Name
Function Description
0
NOP (No Operation)
Disables the My Function feature.
1
ST
Execute data read/transfer.
2
STN
Execute inverted data read/transfer.
3
AND
Logical product of A AND B.
4
ANDN
Logical product of A AND B.
5
OR
Logical sum of A OR B.
6
ORN
Logical sum of A OR B.
7
EQ
Compares data — Outputs 1 if Equal; 0 if not Equal.
8
NE
Compares data — Outputs 0 if Equal; 1 if not Equal.
9
GT
Compares data — Outputs 1 if A>B; 0 if A
B.
10
GE
Compares data — Outputs 1 if A
B; 0 if A
B.
11
LT
Compares data — Outputs 1 if A
B; 0 if A
B.
12
LE
Compares data — Outputs 1 if A
B; 0 if A>B.
13
ASUB
Outputs absolute difference between A and B — |A–B|
14
FB_ON_DELAY
(Timer)
Enables the On response time delay settings of
My Function Time Data 1
–
5
(
F928
–
F932
) for
My Function Data
.
15
FB_OFF_DELAY
(Timer)
Enables the Off response time delay settings of
My Function Time Data 1
–
5
(
F928
–
F932
) for
My Function Data
.
16
FB_COUNTER1
(Timer)
Outputs a 1 upon reaching the pulse count setting of
F933
.
17
FB_COUNTER2
(Timer)
Outputs a 1 upon reaching the pulse count setting of
F934
.
18
FB_PEEK_HOLD
Outputs the peak output value since powering up or since the last reset.
19
SET
Sets data.
20
RESET
Resets data.
21
CLR
Clears data.
22
CLRN
Retains data.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com