Q9 Plus ASD Installation and Operation Manual
247
Alarms and Trips
Alarms
An
Alarm
is an indication that there is a system operating limit that is being exceeded and that a
Fault
may be imminent (not all ongoing alarms result in a fault) or to provide an indication that an operator error
has occurred. An
Alarm
may be associated with an output terminal to notify the operator of the condition
remotely, close a contact, or to engage a brake. At the least, an
Alarm
will cause an alarm code to appear
on the EOI display
The active alarm may be displayed on the
Alarm
screen — some alarms are displayed on the
Frequency
Command
screen. Press the
Mode
key if the alarm is displayed on the
Frequency Command
screen to
scroll to the
Alarm
screen.
Table 18
lists the
Alarm
codes that may be displayed during operation of the
Q9 Plus ASD
. Each alarm
code listed is accompanied by a description and a possible cause. In the event that the source of the
malfunction cannot be determined, contact the TIC Customer Support Center for further information on
the condition and for an appropriate course of action.
In the event that multiple alarms are activated, only the first to be detected will be displayed.
Table 18. Alarms
LED
Screen
LCD
Screen
Alarm Description
Possible Cause
4-20 mA
4-20 mA
4-20 Signal Loss.
• Misconnection, poor connection, or broken
wire.
• Improper programming at
F201
and associated
parameters.
*OL1
*ASD Overload
Load Requirement in
Excess of the Capability
of the ASD.
• Carrier frequency is too high.
• Excessive load.
• Acceleration time is too short.
• DC damping rate is too high.
• Motor is starting into a spinning load after a
momentary power failure.
• ASD is improperly matched to the application.
CM1
Comm Error
Communication Error
Interruption.
• Improperly programmed ASD.
• Improper communications settings.
• Improperly connected cables.
CM2
Comm Error 2
Communication Error.
DAMP
Damp
Damper Closed.
• Improper configuration/programming for
Damper Control at discrete input terminals.
* Reset ignored if active.
Alarm