248
Q9 Plus ASD Installation and Operation Manual
*OP
*DC Over-Volts
DC Bus Voltage Exceeds
Specifications.
• ASD is attempting to start into a spinning
motor after a momentary power loss.
• Incoming commercial power voltage level is
above the specified range.
• Deceleration time is too short.
• Voltage spikes at the 3-phase input; install
inductive filter.
• Over-Voltage Stall feature is turned off.
• System is regenerating.
• Load fluctuations.
*POFF
*DC Under-Volts
Under-Voltage Condition
at the 5, 15, or the 24
VDC supply.
• Defective control board.
• Excessive load on power supply.
• Low input voltage.
E
Emergency Off
Emergency Off.
• Stop-Reset was pressed twice at the EOI.
• E-OFF command was received remotely.
HLD
Heavy Load
Motor/ASD Over Loaded.
• Acceleration time is too short.
• ASD is improperly matched to the application.
• Excessive load.
LLD
Light Load
Light Load.
• ASD is improperly matched to the application.
LLT
Lower Limit
Lower-Limit Time.
• Parameter
F256
adjustment is required.
MOFF
Main Under-Volts
Under-Voltage (Main
Circuit Power Supply).
• 3-phase input voltage low.
• Defective control board.
• Excessive load on power supply.
• Under-Voltage/Ridethrough settings require
adjustment.
OLM
Motor Overload
Motor Overload.
• V/f setting requires adjustment.
• Motor is locked.
• Continuous operation at low speed.
• Motor is improperly matched to the load.
* Reset ignored if active.
Table 18. Alarms (Continued)
LED
Screen
LCD
Screen
Alarm Description
Possible Cause