18
Q9 Plus ASD Installation and Operation Manual
Figure 4. The
Grounding Capacitor
Switch
is used on typeforms —
200-volt
0.5 HP to 10 HP and the 25 and 30 HP/
460-volt
1.0 HP to 250 HP.
The value may be set to
Maximum
(default setting) or to
Zero
by pushing or
pulling the switch actuator, respectively.
Figure 5. The
Grounding Capacitor
Switch
is used on typeforms —
200-volt
15 HP to 20 HP and the 40 HP to 60 HP/
460-volt
30 HP to 100 HP.
The value may be set to
Large
(default
setting) or
Small
by pushing or pulling
the switch actuator, respectively.
Figure 6. The
Grounding Capacitor Bar
is used on typeforms —
200-volt
75 HP
and the 100 HP/
460-volt
125 HP and the
150 HP. The value may be set to
Large
or
Small
(default setting) by connecting
or disconnecting the switching bar,
respectively.
Figure 7. The
Grounding Capacitor
Screw
is used on typeforms —
460-volt
175 HP and above.
The value may be set to
Large
or
Small
(default setting) by placing the screw in
the
A
position or by placing the screw in
the
B
position, respectively.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com