Q9 Plus ASD Installation and Operation Manual
Cable/Terminal Specifications
Installation should conform to NEC Article 110
(Requirements for Electrical Installations), all regulations of
the Occupational Safety and Health Administration, and any other applicable national, regional, or
industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the
Q9 Plus ASD
. Application-specific applicables, wire
insulation type, conductor material, and local and regional regulations are but a few of
the considerations when selecting the actual lug and wire type to be used with the Q9
Plus ASD.
Note:
Cable/Terminal specifications are based on the rated current of the
Q9 Plus ASD
and
Do Not
include the 10% Service Factor.
Note:
Use only 75° C copper wire/cable for motor and power connections.
Table 25. 230-Volt Q9 Plus ASD Cable/Terminal/Torque Specifications.
Model
Number
Wire/Cable Size
Lug Size Range
Terminal
Board Wire
Size
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-Capacity for
Input/Output Power
In-Lbs./N·m
Recommended
Maximum
3Ø-Input
3Ø-Output
TB1 – 4
Terminals
3Ø-Input 3Ø-Output
2015
14
10
14 to 10
20
(3-core shield)
Torque to 5.3/0.6
12.4/1.4
2025
14
10
2035
14
10
2055
10
10
2080
8
8
12 to 8
26.6/3
2110
8
8
10 to 4
2160
6
3
8 to 2
47.8/5.4
2220
4
3
2270
3
3
4 to 1/0
212/24
2330
2
2
2400
1/0
4/0
2 to 300
360/41