42
Q9 Plus ASD Installation and Operation Manual
EOI Command Mode
The
EOI Command
mode is accessed by pressing the
ESC
key from the
Frequency Command
screen.
With the exception of the
Virtual Linear Pump Control Enable/Disable
, the control settings of the
EOI
Command
menu are effective for
EOI
control only.
The
EOI Command
mode provides quick access to the following menu parameters:
Direction
—
Forward
or
Reverse
.
Stop Pattern
— The
Decel Stop
or
Coast
Stop
setting determines the method used to stop the
motor when using the
Stop-Reset
key of the
EOI
. The
Decel Stop
setting enables the
DC Injection
Braking
system setup at
F250
,
F251
, and
F252
. The
Coast Stop
setting allows the motor to stop at
the rate allowed by the inertia of the load.
Note:
The
Stop Pattern
setting has no effect on the
Emergency Off
settings of
F603
.
V/f Group
— One of four
V/f
profiles may be selected and run. Each
V/f
profile is comprised of four
user settings:
Base Frequency
,
Base Frequency Voltage
,
Manual Torque Boost
, and
Electronic
Thermal Protection
. Expanded descriptions of these parameters may be found in the section titled
Direct Access Parameter Information on pg. 82
.
Accel/Decel Group
— One of two
Accel/Decel
profiles may be selected and run. Each of the
Accel/Decel
profiles is comprised of three user settings:
Acceleration
,
Deceleration
, and
Pattern
.
Expanded descriptions of these parameters may be found in the section titled
Direct Access
Parameter Information on pg. 82
(see
F009
).
PID Control
— This setting enables or disables the
PID
feedback function.
Torque Limit Group
— This group is used to select preset positive torque limits to apply to the
active motor (of a multiple motor configuration). The settings may be accessed at
F440
,
F441
,
F442
,
and
F443
, respectively.
VLP Technology Control
— This setting enables or disables the
Virtual Linear Pump
function.