Q9 Plus ASD Installation and Operation Manual
Startup Wizard Requirements
The
Startup Wizard
assists the user with the initial configuration of the
Q9 Plus ASD
by querying the
user for information on the ASD control settings, motor ratings, and ASD display units. The Q9 Plus ASD
may also be setup by directly accessing each of the settings via the
Program
menu or by using the
Direct
Access Number
of each parameter.
Upon initial system power up, the
Startup Wizard
starts automatically and the Welcome screen is
displayed. Click
Next
to continue with the
Startup Wizard
or click
Exit
to go to the
Wizard Finished!
screen.
Running the Startup Wizard
Input the required information into the following screens to complete the
Startup Wizard
.
1. Voltage and Frequency Rating of the Motor
Motors are designed and manufactured for operation
within a specific voltage and frequency range. The
voltage and frequency specifications for a given motor
may be found on the nameplate of the motor.
Settings:
0 — 200 v, 50 Hz
1 — 200 v/230 v, 60 Hz
2 — 380v-480v, 50/60 Hz
2. Upper-Limit Frequency
This parameter sets the highest frequency that the
Q9
Plus ASD
will accept as a frequency command or
frequency setpoint. The Q9 Plus ASD may output
frequencies greater than the
Upper-Limit Frequency
(but, less than the Maximum Frequency) when
operating in the
PID Control
mode,
Torque Control
mode, or the
Vector Control
modes (sensorless or
feedback).
3. Lower-Limit Frequency
This parameter sets the lowest frequency that the
Q9
Plus ASD
will accept as a frequency command or
frequency setpoint. The Q9 Plus ASD will output
frequencies lower than the
Lower-Limit Frequency
when accelerating to the lower limit or decelerating to
a stop. Frequencies below the
Lower Limit
may also
be output when operating in the
PID Control
mode,
Torque Control
mode, or the
Vector Control
modes (sensorless or feedback).