Q9 Plus ASD Installation and Operation Manual
69
4. Automatic Acceleration/Deceleration
When enabled, the
Q9 Plus ASD
adjusts the
acceleration and deceleration rates according to the
applied load. The acceleration and deceleration times
range from 12.5 to 800% of the programmed values
[e.g., Acceleration Time 1 (
F009
) and Deceleration
Time 1 (
F010
) adjusted for the active Accel/Decel
times].
Settings:
0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC only
The motor and the load must be connected prior to selecting
Automatic Accel/Decel
.
If
Automatic Accel/Decel
is not enabled, the
Acceleration
screen will appear followed by the
Deceleration
screen as shown below.
5. Volts Per Hertz Control Type
This function establishes the relationship between the
output voltage and the output frequency of the ASD.
Settings:
0 — Constant Torque
1 — Voltage Decrease Curve
2 — Automatic Torque Boost
3 — Sensorless Vector Control (speed)
5 — V/f 5-Point Setting (open 5-point setting window)
6 — PM Drive
7 — PG Feedback Vector Control (speed)
9 — Energy Saving
10 — Advanced Energy Saving
6. Motor Current Rating
This parameter allows the user to input the full-load
amperage (FLA) of the motor. This value is used by
the
Q9 Plus ASD
to determine the
Motor Overload
Protection
setting for the motor and may be found on
the nameplate of the motor.
Deceleration Time
Acceleration Time
Accelerati
on Time
Decelerati
on Time