Q9 Plus ASD Installation and Operation Manual
7. Motor Rated Speed
This parameter allows the user to input the rated speed
of the motor in RPM. This value may be found on the
nameplate of the motor.
8. Command Source
This selection establishes the source of the
Run
commands (e.g., F, R, Stop, etc.).
Settings:
0 — Terminal Board
1 — Panel Keypad
2 — RS485 (2-wire)/EOI Keypad
3 — RS485 (4-wire)/Terminal Board
4 — Communication Option Board
9. Frequency Command Source
This selection establishes the source of the
Frequency
(speed) command.
Settings:
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 (2-wire)/EOI Keypad
6 — RS485 (4-wire)/Terminal Board
7 — Communication Option Board
8 — RX2
9 — Option V/I
10 — UP/DOWN Frequency
11 — Optional RP Pulse Input
12 — Optional High-Speed Pulse Input
10. Display Units
This screen sets the display units for current and
voltage.
Settings:
0 — %
1 — A/V (Amp/Volt)