Q9 Plus ASD Installation and Operation Manual
77
BACnet
®
Inputs, Outputs, and Values
Table 4. BACnet
®
Binary Inputs.
Digital Input
Terminal
Binary Input
Object ID
Object
Name
Description
Status
Access
F
Binary Input #6
(BI6)
F Status
Monitors the status of the F input
terminal (Forward Run Command)
On/Off
R
R
Binary Input #7
(BI7)
R Status
Monitors the status of the R input
terminal (Reverse Run Command)
On/Off
R
ST
Binary Input #8
(BI8)
ST Status
Monitors the status of the ST input
terminal (Standby Command)
On/Off
R
RES
Binary Input #9
(BI9)
RES Status
Monitors the status of the RES input
terminal (Fault Reset Command)
On/Off
R
S1
Binary Input #10
(BI10)
S1 Status
Monitors the status of the S1 input
terminal (Fire-speed Command)
On/Off
R
S2
Binary Input #11
(BI11)
S2 Status
Monitors the status of the S2 input
terminal (Preset Speed 2)
On/Off
R
S3
Binary Input #12
(BI12)
S3 Status
Monitors the status of the S3 input
terminal (Damper Closed Feedback)
On/Off
R
S4
Binary Input #13
(BI13)
S4 Status
Monitors the status of the S4 input
terminal (Emergency Off (NC))
On/Off
R
LI5*
Binary Input #14
(BI14)
LI5 Status
Monitors the status of the LI5 input terminal
On/Off
R
LI6*
Binary Input #15
(BI15)
LI6 Status
Monitors the status of the LI6 input terminal
On/Off
R
LI7*
Binary Input #16
(BI16)
LI7 Status
Monitors the status of the LI7 input terminal
On/Off
R
LI8*
Binary Input #17
(BI17)
LI8 Status
Monitors the status of the LI8 input terminal
On/Off
R
FLA/FLC (FL)
Binary Input #0
(BI0)
FL Status
Monitors the status of the FL output relay
(Any Fault (NC))
On/Off
R
DSA/DSB
(OUT 1)
Binary Input #1
(BI1)
OUT 1
Status
Monitors the status of the OUT 1 output
relay (Open Damper Command)
On/Off
R
OUT 2
Binary Input #2
(BI2)
OUT 2
Status
Monitors the status of the OUT 2 output
relay (Acc or Dec Complete)
On/Off
R
R2*
Binary Input #3
(BI3)
R2 Status
Monitors the status of the R2 output relay
On/Off
R
OUT 5*
Binary Input #4
(BI4)
OUT 5
Status
Monitors the status of the OUT 5 open
collector output
On/Off
R
OUT 6*
Binary Input #5
(BI5)
OUT 6
Status
Monitors the status of the OUT 6 open
collector output
On/Off
R
* The ETB004Z expansion I/O card is required to use this input.
R = Read-only
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com