78
Q9 Plus ASD Installation and Operation Manual
Table 5. BACnet
®
Binary Outputs.
Digital Output
Terminal
Binary Output
Object ID
Object Name
Description
Status
Access
FLA/FLC
(FL)
Binary Output #0
(BO0)
FL Command
Controls the FL output relay
(
F132
= Data Out 1 (NO))
On/Off
C
DSA/DSB
(OUT 1)
Binary Output #1
(BO1)
OUT 1
Command
Controls the OUT 1 output relay
(
F130
= Data Out 2 (NO))
On/Off
C
OUT 2
Binary Output #2
(BO2)
OUT 2
Command
Controls the OUT 2 output relay
(
F131
= Data Out 3 (NO))
On/Off
C
R2*
Binary Output #3
(BO3)
R2 Command
Controls the R2 output relay
(
F138
= Data Out 4 (NO))
On/Off
C
OUT 5*
Binary Output #4
(BO4)
OUT 5
Command
Controls the OUT 5 open collector
output (
F136
= Data Out 5 (NO))
On/Off
C
OUT 6*
Binary Output #5
(BO5)
OUT 6
Command
Controls the OUT 6 open collector
output (
F137
= Data Out 6 (NO))
On/Off
C
* The ETB004Z expansion I/O card is required to use this input.
C = Commandable
Table 6. BACnet
®
Binary Values.
Binary Value
Object ID
Object Name
Description
Status
Access
Binary Value #0
(BV0)
Run/Stop Status
Indicates the running status of the drive
Runs/Ready
R
Binary Value #1
(BV1)
Fwd/Rev Status
Indicates the rotation direction of the drive
Rev/Fwd
R
Binary Value #2
(BV2)
Fault Status
Indicates the fault status of the drive
Faulted/None
R
Binary Value #4
(BV4)
Hand/Auto
Status
Indicates if the drive is being locally controlled
Hand/Auto
R
Binary Value #6
(BV6)
Maint Req
Indicates if the cumulative run timer has expired
Yes/No
R
Binary Value #7
(BV7)
Drive Ready
Indicates if the drive is ready to run
(ST and Run Command)
Ready/
Not Ready
R
Binary Value #8
(BV8)
At Set-Point
Indicates if the drive has reached its target speed
Reached/No
R
Binary Value #10
(BV10)
Run/Stop Cmd
Commands the drive to start
Start/Stop
C
Binary Value #11
(BV11)
Fwd/Rev Cmd
Commands the rotation direction of the drive
Rev/Fwd
C
R = Read-only; C = Commandable
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com