Q9 Plus ASD Installation and Operation Manual
79
Binary Value #14
(BV14)
Fault Reset
Commands the drive to reset a fault
Reset/No
C
Binary Value #18
(BV18)
Preset Spd 1
Commands the Preset Speed 1 operation
SP1/None
C
Binary Value #19
(BV19)
Preset Spd 2
Commands the Preset Speed 2 operation
SP2/None
C
Binary Value #20
(BV20)
Preset Spd 3
Commands the Preset Speed 3 operation
SP3/None
C
Binary Value #21
(BV21)
Freq Ovrd
Overrides the Frequency Mode 1 (
F004
) selection
Enabled/Off
C
Binary Value #22
(BV22)
Cmd Ovrd
Overrides the Command Mode (
F003
) selection
Enabled/Off
C
R = Read-only; C = Commandable
Table 7. BACnet
®
Analog Inputs.
Analog Input
Terminal
Analog Input
Object ID
Object Name
Description
Value
Access
RR
Analog Input #0
(AI0)
RR Level
Input level of the RR analog input
Percent (%)
of full scale
R
V/I
Analog Input #1
(AI1)
V/I Level
Input level of the V/I analog input
Percent (%)
of full scale
R
RX
Analog Input #2
(AI2)
RX Level
Input level of the RX analog input
Percent (%)
of full scale
R
AI1*
Analog Input #3
(AI3)
AI1 Level
Input level of the AI1 analog input
Percent (%)
of full scale
R
AI2*
Analog Input #4
(AI4)
AI2 Level
Input level of the AI2 analog input
Percent (%)
of full scale
R
* The ETB004Z expansion I/O card is required to use this input.
R = Read-only
Table 6. BACnet
®
Binary Values. (Continued)
Binary Value
Object ID
Object Name
Description
Status
Access
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com