80
Q9 Plus ASD Installation and Operation Manual
Table 8. BACnet
®
Analog Outputs.
Analog
Output
Terminal
Analog Output
Object ID
Object Name
Description
Value
Access
FM
Analog Output #0
(AO0)
FM Command
Controls the FM analog output
terminal (
F005
= Data From Comm)
Percent (%)
of full scale
W
AM
Analog Output #1
(AO1)
AM Command
Controls the AM analog output
terminal (
F670
= Data From Comm)
Percent (%)
of full scale
W
MON1*
Analog Output #2
(AO2)
MON1
Command
Controls the MON1 analog output
terminal (
F672
= Data From Comm)
Percent (%)
of full scale
W
MON2*
Analog Output #3
(AO3)
MON2
Command
Controls the MON2 analog output
terminal (
F674
= Data From Comm)
Percent (%)
of full scale
W
* The ETB004Z expansion I/O card is required to use this input.
W = Writable
Table 9. BACnet
®
Analog Values.
Analog Value
Object ID
Object Name
Description
Value
Access
Analog Value #0
(AV0)
Output Speed
Output speed (output frequency / base frequency
x motor nameplate rpm, ie. 30 / 60 x 1770 = 885)
RPM
R
Analog Value #1
(AV1)
Output Freq
Frequency output
Hz
R
Analog Value #2
(AV2)
DC Bus Volt
DC bus voltage
V
R
Analog Value #3
(AV3)
Output Volt
Voltage output to the motor
V
R
Analog Value #4
(AV4)
Output Current
Current generated by the motor
A
R
Analog Value #5
(AV5)
Output Torque
Torque generated by the motor
%
R
Analog Value #6
(AV6)
Input Power
Power consumed by the drive
kW
R
Analog Value #7
(AV7)
Output Power
Power consumed by the motor
kW
R
Analog Value #8
(AV8)
Total Input Power
Total cumulative power consumed by the drive
kWh
R
Analog Value #9
(AV9)
Total Output Power
Total cumulative power consumed by the motor
kWh
R
Analog Value #10
(AV10)
PID Fbck
PID feedback value
Hz
R
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com