Q9 Plus ASD Installation and Operation Manual
81
Analog Value #11
(AV11)
Run Time
Total time of operation
Hours
R
Analog Value #12
(AV12)
VLP Technology
Average
Average operating Virtual Linear Pump number
-
R
Analog Value #13
(AV13)
VLP Technology
Feedback
Virtual Linear Pump process feedback
-
R
Analog Value #14
(AV14)
VLP Technology
Direct Ref
Virtual Linear Pump direct mode command reference
-
C
Analog Value #15
(AV15)
VLP Technology
Process Hold Ref
Virtual Linear Pump process hold mode command
reference
-
C
Analog Value #16
(AV16)
Freq Ref
Frequency reference
Hz
C
Analog Value #18
(AV18)*
Last Flt
Current fault code
-
R
Analog Value #19
(AV19)*
Prev Flt 1
Most recent fault code
-
R
Analog Value #20
(AV20)*
Prev Flt 2
Second most recent fault code
-
R
Analog Value #23
(AV23)
Accel Time 1
Changes Acceleration Time 1 (
F009
)
Sec
W
Analog Value #24
(AV24)
Decel Time 1
Changes Deceleration Time 1 (
F010)
Sec
W
* Refer to the
BACnet
®
Option Unit Function Manual
for the list of fault codes.
R = Read-only; C = Commandable; W = Writable
Table 9. BACnet
®
Analog Values. (Continued)
Analog Value
Object ID
Object Name
Description
Value
Access
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com