84
Q9 Plus ASD Installation and Operation Manual
FM Terminal Function
Program
Terminal
Analog Output Terminals
This setting determines the output function of the
FM
analog output terminal.
The
FM
output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal (select
current or voltage at
F681
). The available assignments for this output terminal
are listed in
Table 11 on pg. 237
.
Note:
If the monitored item has a positive and a negative component,
use the
Expansion I/O Card 2
(P/N ETB004Z). See the
Expansion IO Card Option 2
instruction manual (P/N 58686)
for additional information on the function of the option card.
See
F678
and
F684
for additional information on this parameter.
To read
Voltage
at this terminal, connect a 100 – 500
resistor from FM (+) to
CC
(-). The voltage is read across the 100 – 500
resistor.
To read
Current
at this terminal, connect a 100 – 500
resistor in series from
FM (+), through the current meter, to
CC
(-).
FM Terminal Setup Parameters
F005
— Set FM Function
F006
— Calibrate FM Terminal
F681
— Voltage/Current Output Switching Selection
F682
— Output Response Polarity Selection
F683
— Set Zero Level
Direct Access Number — F005
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
FM Output Terminal Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to calibrate the
FM
analog output.
To calibrate the
FM
analog output, connect a meter (current or voltage) as
described at
F005
.
With the ASD running at a known value (e.g., output frequency), adjust this
parameter until the assigned function produces the desired DC level output at
the
FM
output terminal.
See
F005
for additional information on this parameter.
Direct Access Number — F006
Parameter Type —
Numerical
Factory Default —
236
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
F005
F006
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com