Q9 Plus ASD Installation and Operation Manual
85
Type Reset
Program
Utilities
Type Reset
This feature assists the user when performing fault analysis or by allowing a
quick system setup change when required. Performing a
Type Reset
results in
one of the following user-selected post-Reset configurations.
Settings:
0 — None
1 — 50 Hz Setting
2 — 60 Hz Setting
3 — Reset to Factory Settings
4 — Clear Past Trips
5 — Clear Run Timer
6 — Initialize Typeform
7 — *Save User Settings
8 — Restore User Settings
9 — Clear Cumulative Fan Timer
10 — ACC/DEC Unit 0.01s (FA09=0)
11 — ACC/DEC Unit 0.1s (FA09=1)
12 — Set EOI Memory to Default
Note:
User settings that are stored in the memory of the EOI are not
saved via the
Save User Settings
selection. The unsaved
functions include the
EOI Option Setups
, (Utilities
Display Parameters
, and (Monitor Setup
)
Scrolling
Monitor Select
.
Direct Access Number — F007
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
No
Forward/Reverse Run
Program
Fundamental
Standard Mode Selection
While operating in the
Hand
mode, this parameter sets the direction of motor
rotation.
From the
Frequency Command
screen, press the
ESC
key. At the subsequent
EOI Command
screen, select the
Direction
field and change the setting. Press
the
Rotary Encoder
and the new setting will be in effect.
This setting
will not override parameter
F311
(Forward/Reverse Disable).
If either direction is disabled via parameter
F311
, the disabled direction will not
be recognized if commanded by the keypad. If both directions are disabled via
parameter
F311
, the direction command from the keypad will determine the
direction of the motor rotation.
Settings:
0 — Forward
1 — Reverse
2 — Forward (Switchable F/R by Keypad)
3 — Reverse (Switchable F/R by Keypad)
Direct Access Number — F008
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
Yes
Reset
Save User
Settings
F007
F008