86
Q9 Plus ASD Installation and Operation Manual
Acceleration Time 1
Program
Fundamental
Accel/Decel 1 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the
Maximum Frequency
for the
Acceleration 1
profile. The
Accel/Decel pattern may be set using
F502
.
Note:
An acceleration time shorter than that which the load will allow
may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel
,
Stall
, and
Ridethrough
settings
may
lengthen the acceleration times.
Acceleration
The acceleration rate of a motor is determined by several factors: applied
power, applied load, and the physical properties of the motor (winding
parameters, motor size, etc.). The ASD will control the first of these factors:
input power. The settings of the ASD will control the frequency and amplitude
of the applied voltage to the motor.
Under most operating conditions, as the output frequency of the ASD goes up
so does the output voltage (linear acceleration). The ASD has the ability to
modify the relationship between frequency and voltage automatically to
produce smoother operation or increased (starting) torque (see
F502
).
Direct Access Number — F009
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Deceleration Time 1
Program
Fundamental
Accel/Decel 1 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the
Maximum Frequency
to 0.0 Hz for the
Deceleration 1
profile. The
Accel/Decel Pattern
may be set using
F502
.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic
Accel/Decel
,
Stall
, and
Ridethrough
settings
may lengthen the
deceleration times.
Direct Access Number — F010
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Maximum Frequency
Program
Fundamental
Frequency Settings
This setting determines the absolute maximum frequency that the ASD can
output.
Accel/Decel
times are calculated based on the
Maximum Frequency
setting.
The
Maximum Frequency
is not limited by this setting while operating in the
Drooping Control
mode (see
F320
).
Note:
This setting may not be lower than the
Upper-Limit Frequency
(
F012
)
setting
.
Direct Access Number — F011
Parameter Type —
Numerical
Factory Default —
80.00
Changeable During Run —
No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — Hz
Upper-Limit Frequency
Program
Fundamental
Frequency Settings
This parameter sets the highest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD may output frequencies
higher than the
Upper-Limit Frequency
(but, lower than the
Maximum
Frequency
) when operating in the
PID Control
mode,
Torque Control
mode,
or the
Vector Control
modes (sensorless or feedback).
Note:
This setting may not be higher than the
Maximum Frequency
(
F011
)
setting.
Direct Access Number — F012
Parameter Type —
Numerical
Factory Default —
66.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
F011
)
Units — Hz
F009
F012
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com