88
Q9 Plus ASD Installation and Operation Manual
Manual Torque Boost 1
Program
Fundamental
Motor Set 1
The
Manual Torque Boost 1
function is used to increase the low frequency
torque for high-inertia loads by increasing the output voltage at frequencies
below ½ of the
Base Frequency 1
(
F014
) setting.
The value programmed as a boost percentage establishes an output voltage vs.
output frequency relationship to be used to start the motor or to provide
smoother operation.
Note:
Setting an excessive
Torque Boost
level may cause nuisance
tripping and mechanical stress to loads.
Direct Access Number — F016
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Motor Overload Protection Configuration
Program
Protection
Overload
This parameter is used to enable the
Soft Stall
feature which protects the motor
from an over-current condition by reducing the output frequency during a
temporary increased current requirement from the load.
A V/f motor may be specified here along with the
Overload Stall
to better
match the ASD to the application.
This parameter setting may extend the
Over-Voltage
Stall
time settings.
Settings:
0 — Motor Overload Trip without Soft Stall
1 — Motor Overload Trip with Soft Stall
2 — Without Motor Overload Trip or Soft Stall
3 — Soft Stall Only
4 — V/f Motor Overload Trip without Soft Stall
5 — V/f Motor Overload Trip with Soft Stall
6 — V/f Motor without Overload Trip or Soft Stall
7 — V/f Motor Soft Stall Only
Direct Access Number — F017
Parameter Type —
Selection List
Factory Default —
Motor Overload Trip
with Soft Stall
Changeable During Run —
Yes
F016
F017