Q9 Plus ASD Installation and Operation Manual
89
Preset Speed 1
Program
Frequency
Preset Speeds
Up to fifteen (15) output frequency values that fall within the
Lower-Limit
and
the
Upper-Limit
range may be programmed into the ASD and output as a
Preset Speed
. This parameter assigns an output frequency to binary number
0001 and is identified as
Preset Speed 1
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
.
Perform the following setup to allow the system to receive
Preset Speed
control input at the
S1 – S4
terminals:
1.
Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board
.
2.
Program
Terminal
Input Terminals
S1
(set to
Preset Speed 1
;
LSB of 4-bit count). Repeat for
S2
–
S4
(MSB of 4-bit count) as
Preset
Speed 2
–
4
, respectively (all
Normally Open
).
3.
Program
Frequency
Preset Speeds
Preset Speed
1
(set an output
frequency as
Preset Speed 1
; repeat for
Preset Speeds 2
–
15
as required).
4.
Place the system in the
Auto
mode (Hand/Auto LED Off).
5.
Provide a
Run
command (connect F and/or R to CC).
Connect
S1
to
CC
to run
Preset Speed 1
(
S1
to
CC
= 0001 binary).
With
S1
–
S4
configured to output
Preset Speeds
(
F115
–
F118
), 0001 – 1111
may be applied to
S1 – S4
of the
Terminal Board
to run the associated
Preset
Speed
.
If bidirectional operation is required,
F
and
R
must be connected to
CC
.
With
S1
being the least significant bit of a binary count, the
S1 – S4
settings
will produce the programmed speed settings as indicated in the
Preset Speed
Truth Table
to the right.
Direct Access Number — F018
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — Lower-Limit Freq. (
F013
)
Maximum — Upper-Limit Freq. (
F012
)
Units — Hz
Preset Speed Truth Table
Preset Speed 2
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 0010 and is
identified as
Preset Speed 2
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
.
See
F018
for additional information on this parameter.
Direct Access Number — F019
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — Lower-Limit Freq. (
F013
)
Maximum — Upper-Limit Freq. (
F012
)
Units — Hz
eset Speed 1
Preset
S4
MSB
S3
S2
S1
LSB
Output
1
0
0
0
1
F018
2
0
0
1
0
F019
3
0
0
1
1
F020
4
0
1
0
0
F021
5
0
1
0
1
F022
6
0
1
1
0
F023
7
0
1
1
1
F024
8
1
0
0
0
F287
9
1
0
0
1
F288
10
1
0
1
0
F289
11
1
0
1
1
F290
12
1
1
0
0
F291
13
1
1
0
1
F292
14
1
1
1
0
F293
15
1
1
1
1
F294
Note:
1 = Terminal connected to
CC
.
eset Speed 2
F018
F019