106
Switches and connectors on the circuit board
Remove the 4 screws to detach the electrical control cover.
* Refer to “9 Installation Method for Each System Configuration” on page 109 about setting the switch.
Screws (x 4)
Electrical control cover
Electrical control base
1
ON
2
3
4
1
ON
2
3
4
SW702
SW703
1
ON
2
SW 301
1
ON
2
SW 701
ON
OFF
ON
OFF
ON
OFF
CN705(5P)
CN706(2P)
Changeover switch
for the terminator
SW301 (No.1)
100
ȍ
: ON
None: OFF
Changeover switch
for the central
control address
SW703 (No. 3)
Fix: ON
Auto: OFF
Changeover switch
for the group
address
SW703 (No.4)
Header (Individual:
ON
Follower: OFF
Changeover switch for
pulse/static
SW701 (No.1)
Pulse: ON
Level: OFF
Connectors for the external
input
Remote ON/OFF adapter
(NRB-1HE: sold separately)
No voltage a-contact input
(Remote controller
operation Invalid/Valid,
fan speed Low/High,
Ventilation mode Bypass/
Heat exchange, Operation
ON/OFF)
Voltage of DC12V or 24V
(ON/OFF)
Changeover switch for the
indoor unit address
SW702 (No.1 to 4), 703 (No. 1
and 2)