118
Central control system (When controlling the air conditioner and Air to Air Heat Exchanger
together)
Changing the group address (No.4 of SW703)
The settings of the group address does not need to be adjusted. Leave the value “Follower: OFF”. (Factory default:
Follower)
* The settings of the follower unit with the smallest indoor unit address number reflect the indication of the remote
controller.
Changing the indoor unit address (No.1 to 4 of SW702, No.1 and 2 of SW703)
Settings for changing the indoor unit address are necessary. Do not duplicate the value. (1 to 64) (Factory default: 1)
Changing the terminator (No.1 of SW301)
* The settings do not need to be adjusted.
• For the settings of the central control address, refer to the Installation Manual of the central control device.
• Do not perform the central control wiring with the Air to Air Heat Exchanger.
F
L
N
A B
L
N
L
N
L
N
A B
A B
U1
U3
U2
U4
A B
U1 U2
A B
U1 U2
L
N
U1
U3
U2
U4
A B
U1
U3
U2
U4
L1 L2 L3 N
U1 U2 U3 U4 U5 U6
* For group control with air conditioners, perform inter-unit wiring between the units.
* Up to 8 units can be installed for group control.
Remote controller
(follower)
Remote controller
(header)
Power supply
Indoor unit
Power
supply
Power
supply
Power
supply
Power
supply
Indoor unit
Air to Air Heat
Exchanger
Air to Air Heat
Exchanger
Power supply
Central controller
Outdoor unit
Control wiring between indoor and outdoor units
Control wiring between indoor units
Remote controller
inter-unit wiring
Central
control
wiring