– 8 –
Air to Air Heat Exchanger
Installation Manual
EN
Air to Air Heat Exchanger
Installation Manual
Connection diagram
1. The dotted line represents a wire procured locally, and the dashed line represents an option sold separately.
2.
represents a terminal block,
represents a connection terminal, and
represents a connector on
the printed circuit board.
3.
represents a protective earth.
4.
represents a printed circuit board.
5. Using a no voltage a-contact input of the external input (sold separately), the following operations are available:
Between 1 and 2: Selecting the remote controller operation (Invalid/Valid)
Between 1 and 3: Adjusting the ventilation fan speed (Low/High)
Between 1 and 4: Selecting the ventilation mode (Bypass mode/Heat exchange mode)
Between 1 and 5: Operation (ON/OFF)
Use a microcurrent contact (DC12V, 1mA). In addition, ON/OFF operation is possible when using a voltage of
DC12V or 24V.
6. Blue wire (High) is connected as factory default. To switch to “Extra High”, connect black wire’s connector
instead of blue.
7. When the temperature of the outdoor air is below -10°C, the unit runs in the cold mode (the ventilator for air
supply runs intermittently). The unit cannot run when the temperature of the outdoor air is below -15°C. The
ventilator for air supply stops running and the ventilator for air exhaust also stops depending on the settings.
8. Even if “Bypass mode” is selected manually, the unit switches to “Heat exchange mode” automatically to prevent
condensation when the temperature of the outdoor air is below 15°C. However, “Bypass mode” is still displayed.
TRA
SW301
CN105
1
SW701
RY
7
0
1
RY
7
0
4
S(N)
R(L)
TB1
CN67
1
3
ON
OFF
1
SW702
+
+
OFF
DC 5V
DC20V
DC12V
ON
U4
TB2 U3
B
A
2
OFF
CN040
1
4
3
2
2 3 4
1
2
1
3 CN041
OFF
ON
SW703
ON
CN106
1
2
t°
TOA
t°
1
7
43F22
3
43F12
5
2
3
43F11
5
1
3
5
5
43F21
1
3
2
C
C
P01
CN701
8
43F12
FM1
M
1~
M
1~
M
FM2
7
7
7
CN704
RY
7
0
5
RY
7
0
2
3
5
1
3
CN760
5
2
1
3 4
RY
7
0
9
RY
7
0
8
RY
7
1
0
6
5
1
3
9
7
5
6
CN702
43F21
8
8
8
43F11
43F22
DAM
3
1
2
4
5 TB3
4
CN705
2
1
3
CN706
1
5
2
1
5
2
2
B
A
Power supply for the Air
to Air Heat Exchanger
220-240V~, 50Hz
220V~, 60Hz
Earth
Air to Air Heat
Exchanger
represents the connector to switch between
Extra High and High.
Wiring for central control
Wiring for the remote
controller
Wired remote
controller (sold
separately)
Indoor control
circuit board
MCC1615
Connector
(White)
White
Connector
(Black)
White
Or
ang
e
External output
(220-240V~, under 1A each)
*5 External input (sold
separately)
No voltage a-contact input
Voltage DC (12V, 24V) input
Operation output
White
Wh
ite
Wh
ite
Re
d
Re
d
White
Red
Bl
ue
Bl
ac
k
Connector
(White *6)
White
Yellow
Yellow
Black
Br
own
Blu
e
Bl
ac
k
Connector
(Red *6)
Wh
it
e
Re
d
(White)
Gray
Light blue
Gra
y
Ye
llow
Bl
ue
Li
gh
t bl
u
e
Pi
nk
Bro
w
n
Wh
ite
Ye
llow
Bl
ue
Bl
ac
k
Re
d
(White)
(Red)
1 Common
2 Remote controller operation
3 Ventilation fan speed
4 Ventilation mode
5 Operation
(Black)
Power
supply
(Blue)
(Blue)
(Brown)
(White)
Black
Blue Blue
Black
F01
T3.15A
250V~
Common
External damper output
Abnormal/Bypass mode output
Code
Part name
CN***
Connector
F01
Fuse
FM1
Air supplying motor
FM2
Air exhausting motor
DAM
Damper motor
TRA
TRA sensor
Code
Part name
TOA
TOA sensor
RY701, RY702
Relay for air supplying motor
RY704, RY705
Relay for air exhausting motor
TB1
Terminal block (power supply)
TB2
Terminal block (communication)
TB3
Terminal block (external output)
Code
Part name
SW301, SW701
SW702, SW703
DIP switch
43F11, 43F12
Relay for air supplying motor
43F21, 43F22
Relay for air exhausting motor
Switches and connectors on the circuit board
Remove the 4 screws to detach the electrical control cover.
* Refer to "9. Installation Method for Each System Configuration" on page 10 about setting the switch.
Screws (x 4)
Electrical control cover
Electrical control base
1
ON
2
3
4
1
ON
2
3
4
SW702
SW703
1
ON
2
SW 301
1
ON
2
SW 701
ON
OFF
ON
OFF
ON
OFF
CN705(5P)
CN706(2P)
Changeover switch
for the terminator
SW301 (No.1)
100
Ω
: ON
None: OFF
Changeover switch
for the central
control address
SW703 (No. 3)
Fix: ON
Auto: OFF
Changeover switch
for the group
address
SW703 (No.4)
Header (Individual:
ON
Follower: OFF
Changeover switch for
pulse/static
SW701 (No.1)
Pulse: ON
Level: OFF
Connectors for the external
input
Remote ON/OFF adapter
(NRB-1HE: sold separately)
No voltage a-contact input
(Remote controller
operation Invalid/Valid,
fan speed Low/High,
Ventilation mode Bypass/
Heat exchange, Operation
ON/OFF)
Voltage of DC12V or 24V
(ON/OFF)
Changeover switch for the
indoor unit address
SW702 (No.1 to 4), 703 (No. 1
and 2)
15-EN
16-EN
+00ET9X463301_01EN.book Page 8 Thursday, January 20, 2011 4:41 PM
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk