Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
101
Jog Frequency
Program
Frequency
Jog Settings
This parameter sets the output frequency of the drive during a Jog.
Jogging is the term used to describe turning the motor on for small
increments of time and is used when precise positioning of motor-driven
equipment is required.
Enabling the Jog Window allows for the Manual Jog window to be
among the screens accessed during repeated MON/PRG entries. This
screen must be displayed when Jogging using the EOI.
The Jog function may be initiated from the EOI or remotely via the
Control Terminal Strip, or using Communications (for additional
information on using Communications for Jogging, see the
Communications manual).
To perform a Jog, set this parameter (
) to the desired Jog
frequency.
Select a Jog Stop method (
Jog Using the EOI
To initiate a Jog from the EOI perform the following:
1. Place a check in the Enable Jog Window box (Program
Fre-
quency Settings
Jog Settings
Enable Jog Window).
Note:The Jog Window must be displayed on the EOI to
perform the Jog function using the EOI.
2. Press MON/PRG to access the Jog Window.
3. Using the Up/Down arrow keys of the EOI, select Reverse or
Forward.
4. Place the system in the Hand mode.
5. Press and hold the Run key for the desired Jog duration.
Jog Using the Control Terminal Strip
To initiate a Jog from the Control Terminal Strip perform the following:
1. Assign a discrete input terminal to the Jog function (see
).
2. Assign a discrete input terminal to the F (Forward) function (and
).
3. Provide a Forward and/or Reverse command from the Control
Terminal Strip.
4. From the Jog Window, use the Up/Down arrow keys of the EOI to
select Reverse or Forward (Program
Frequency Settings
Jog
Settings
Enable Jog Window). Press MON/PRG to access the
Jog Window.
5. Place the system in the Auto mode.
6. Connect the assigned Jog terminal (from step
) to CC for the
desired Jog duration.
Direct Access Number —
F260
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 20.00
Units — Hz