Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
103
Jump Frequency 2 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 2
Direct Access Number —
F273
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency 3
Program
Special
Jump Frequencies
Same as Jump Frequency 1
(
) and is used when multiple
frequencies are to be jumped (see the plus-or-minus value setting at
). When multiple jump frequencies overlap, the system will
recognize the lowest and the highest frequencies as one jump range.
Direct Access Number —
F274
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
Jump Frequency 3 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 3
Direct Access Number —
F275
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency Processing Selection
Program
Special
Jump Frequencies
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See
for additional information on the Jump Frequency settings.
Settings:
0 — Process Amount (use PID feedback)
1 — Output Frequency
Direct Access Number —
F276
Parameter Type —
Selection List
Factory Default —
Process Amount
Changeable During Run —
Yes
Preset Speed 8
Program
Frequency
Preset Speeds
This parameter assigns an output frequency to binary number 1000 and
is identified as Preset Speed 8. The binary number is applied to S1 – S4
of the Control Terminal Strip to output the Preset Speed (see
for
additional information on this parameter).
Direct Access Number —
F287
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — Lower-Limit
(
Maximum — Upper-Limit
(
Units — Hz
Summary of Contents for W7 DN-57442-006
Page 1: ...ADJUSTABLE SPEED DRIVES W7 DN 57442 006 INSTALLATION OPERATION MANUAL June 2020 ...
Page 2: ......
Page 3: ...Document Number 57442 006 Date June 2020 W7 ASD Installation and Operation Manual ...
Page 4: ......
Page 60: ......
Page 221: ......