W7B ASD Installation & Operation Manual
• Store in a well-ventilated covered location
and preferably in the original carton if the
equipment will not be used upon receipt.
• Store in a cool, clean, and dry location. Avoid
storage locations with extreme temperatures,
rapid temperature changes, high humidity,
moisture, dust, corrosive gases, or metal
particles.
• The storage temperature range of the W7B
ASD is 14° to 131° F (-10° to 55° C).
•
DO NOT
store the unit in places that are
exposed to outside weather conditions (i.e.,
wind, rain, snow, etc.).
• Store in an upright position.
Disposal
Never dispose of electrical components via
incineration. Contact your state environmental
agency for details on disposal of electrical
components and packaging in your area.
Installation Precautions
Location and Ambient
Requirements
• The W7B ASD is intended for permanent
installations only.
• The W7B ASD is commercial in design. The
equipment is not intended for use in a
residential environment at any time.
• Installation should conform to the National
Electrical Code — Article 110 (NEC)
(
Requirements For Electrical Installations
), all
regulations of the Occupational Safety and
Health Administration, and any other applicable
national, regional, or industry codes and
standards.
Note: For all references to the National Electrical
Code (NEC), see the latest release of the National
Electrical Code.
• Select a mounting location that is easily
accessible, has adequate personnel working
space, and adequate illumination for
adjustment, inspection, and maintenance of the
equipment (refer to NEC Article 110-13).
•
DO NOT
mount the ASD in a location that
would produce catastrophic results should it
become dislodged from its mounting location
(equipment damage or injury).
•
DO NOT
mount the ASD in a location that
would allow it to be exposed to flammable
chemicals or gases, water, solvents, or other
fluids.
• Avoid installation in areas where vibration,
heat, humidity, dust, fibers, metal particles,
explosive/corrosive mists or gases, or sources
of electrical noise are present.
• The installation location shall not be exposed
to direct sunlight.
• Allow proper clearance spaces for
installation.
DO NOT
obstruct the ventilation
openings. Refer to the section titled
for additional
information on ventilation requirements.
• The ambient operating temperature range of
the W7B ASD is 14° to 104° F (-10° to 40° C).