Direct Access Parameter Information
W7B ASD Installation & Operation Manual
120
https://www.toshiba.com/tic/
Frequency Limit at Position [8001 = diabled] (Hz/Second)
Program
Feedback
PG Settings
While operating in the Position-Control mode and using PG feedback,
this setting determines the maximum acceleration rate in Hz/second.
Direct Access Number —
F373
Parameter Type —
Numerical
Factory Default —
800
Changeable During Run —
Yes
Minimum — 1
Maximum — 8001
Units — Hz/Second
Current Control Proportional Gain
Program
Feedback
PG Settings
This parameter sets the sensitivity of the drive when monitoring the
output current to control speed. The larger the value entered here, the
more sensitive the drive is to changes in the received feedback.
Direct Access Number —
F374
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 100.0
Maximum — 1000
Current Control Integral Gain
Program
Feedback
PG Settings
This parameter sets the degree and rate at which the output frequency
will be allowed to change when prompted by changes in the output
current.
The larger the value entered here, the quicker/more the drive responds
to changes in feedback.
Direct Access Number —
F375
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 100.0
Maximum — 1250
Speed Loop Proportional Gain
Program
Feedback
PG Settings
This parameter sets the Proportional Gain (sensitivity) of the drive when
monitoring the PG signal to control speed. The larger the value entered
here, the more sensitive the drive is to changes in the received feedback
and the quicker it responds.
Direct Access Number —
F376
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 3.2
Maximum — 1000
Speed Loop Integral Gain
Program
Feedback
PG Settings
This parameter sets the response time of the Speed Loop Integral Gain.
The smaller the value here, the more pronounced (quicker) the effect of
the integral function.
Direct Access Number —
F377
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 200.0