Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
129
Speed Limit (torque = 0) Center Value Reference Selection
Program
Torque
Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary
as a function of a changing load while operating in the Torque Control
mode. This parameter sets the input terminal that will be used to control
the allowable speed variance.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F431)
Direct Access Number —
F430
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Speed Limit (torque = 0) Center Value
Program
Torque
Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary
as a function of a changing load while operating in the Torque Control
mode. This parameter sets the targeted speed. The plus-or-minus value
for this setting may be set at
Direct Access Number —
F431
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Max. Freq.
(
Units — Hz
Speed Limit (torque = 0) Band
Program
Torque
Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary
as a function of a changing load while operating in the Torque Control
mode. This parameter sets a plus-or-minus value for the Speed Limit
Torque Level (
).
Direct Access Number —
F432
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Max. Freq.
(
Units — Hz
Speed Limit (torque = 0) Recovery Time
Program
Torque
Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary
as a function of a changing load while operating in the Torque Control
mode. This parameter sets the response time of the system to torque
change requirements.
Direct Access Number —
F433
Parameter Type —
Numerical
Factory Default —
0.20
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds