Direct Access Parameter Information
W7B ASD Installation & Operation Manual
130
https://www.toshiba.com/tic/
Power Running Torque Limit 1
Program
Torque
Torque Limit Settings
This parameter determines the source of the control signal for the
positive torque limit setting. If Setting is selected, the value set at
is
used as the Power Running Torque Limit 1 input.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F441)
Direct Access Number —
F440
Parameter Type —
Selection List
Factory Default —
Setting (F441)
Changeable During Run —
Yes
Power Running Torque Limit 1 Level [250% = disabled]
Program
Torque
Manual Torque Limit Settings
This parameter provides a value for the Power Running Torque Limit 1
setting if Setting is selected at
. This value provides the positive
torque upper-limit for the 1 motor.
Direct Access Number —
F441
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Regenerative Braking Torque Limit 1
Program
Torque
Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal. If Setting is selected, the value set at
is used for this
parameter.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (Option Card)
5 — Setting (F443)
Direct Access Number —
F442
Parameter Type —
Selection List
Factory Default —
Setting (F443)
Changeable During Run —
Yes
Regenerative Braking Torque Limit 1 Level [250% = disabled]
Program
Torque
Manual Torque Limit Settings
This parameter provides a value to be used as the Regeneration Torque
Limit 1 if Setting is selected at
.
Direct Access Number —
F443
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Power Running Torque Limit 2 Level [250% = disabled]
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the 2
motor profile when multiple motors are controlled by a single drive or
when a single motor is controlled by multiple profiles.
Direct Access Number —
F444
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %