S-Curve Acceleration/Deceleration Pattern 1
Program
Special
ACC/DEC 1-4 Settings
This parameter enables a user-selected preprogrammed output profile
that controls the acceleration and deceleration pattern for the Accel/
Decel 1 parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
The figures below provide a profile of the available accel/decel patterns.
Direct Access Number —
F502
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Linear
acceleration and deceleration is the
default pattern and is used on most
applications.
S-Pattern 1
is used for applications that require
quick acceleration and deceleration. This setting
is also popular for applications that require shock
absorption at the start of acceleration or
deceleration.
S-Pattern 2
acceleration and deceleration
decreases the rate of change above the
base frequency.