Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
143
Pattern Run (Not Used)
N/A
The Pattern Run function is not supported with the W7B ASD.
Direct Access Number —
F520
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Motor Overload Protection Level 1
Program
Motor
Motor Set 1
The Motor Overload Protection Level 1 parameter specifies the motor
overload current level for motor set 1. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it
may be set as a percentage of the ASD rating. The name-plated FLA of
the motor may be entered directly when Amps is selected as the unit of
measurement (see
Motor Overload Protection Level settings (1 – 4) will be displayed in
Amps if the EOI display attributes are set to V/A rather than
%
.
Note:
Not used with the W7B ASD.
Direct Access Number —
F600
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 100.0
Units — %
Stall Prevention Level
Program
Protection
Stall
This parameter specifies the output current level at which the output
frequency is reduced in an attempt to prevent a trip. The over-current
level is entered as a percentage of the maximum rating of the drive.
Note:
Parameter
(Soft Stall) must be enabled to use this
feature.
Direct Access Number —
F601
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.0
Units — %
ASD Trip Record Retention Selection
Program
Protection
Trip Settings
This parameter Enables/Disables the Trip Save at Power Down setting.
When enabled, this feature logs the trip event and retains the trip
information when the system powers down. The trip information may be
viewed from the Monitor screen.
When disabled, the trip information will be cleared when the system
powers down.
Settings:
0 — Cleared after power off
1 — Hold after power off
Direct Access Number —
F602
Parameter Type —
Selection List
Factory Default —
Cleared after
power off
Changeable During Run —
No