Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
145
Motor 150% Overload Time Limit
Program
Protection
Overload
This parameter establishes a time that the motor may operate at 150%
of its rated current before tripping. This setting applies the time/150%
reference to the individual settings of each motor (e.g., this setting
references 150% of the
setting for the 1 motor).
The unit will trip sooner than the time entered here if the overload is
greater than 150%.
Direct Access Number —
F607
Parameter Type —
Numerical
Factory Default —
600
Changeable During Run —
Yes
Minimum — 10
Maximum — 2400
Units — Seconds
Suppression of Inrush Current Timing
Program
Protection
Soft Start
This parameter determines the length of the inrush current suppression,
which can be for up to 2.5 seconds.
Direct Access Number —
F609
Parameter Type —
Numerical
Factory Default —
0.30
Changeable During Run —
No
Minimum — 0.30
Maximum — 2.50
Units — Seconds
Low Current Trip Selection
Program
Protection
Low-Current Settings
This parameter Enables/Disables the low-current trip feature.
When enabled, the drive will trip on a low-current fault if the output
current of the drive falls below the level defined at
and remains
there for the time set at
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number —
F610
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Low Current Detection Current
Program
Protection
Low-Current Settings
When the low-current monitor is enabled, this function sets the low-
current trip threshold. The threshold value is entered as a percentage of
the maximum rating of the drive.
Direct Access Number —
F611
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Low Current Detection Time
Program
Protection
Low-Current Settings
When the low-current monitor is enabled, this function sets the time that
the low-current condition must exist to cause a trip.
Direct Access Number —
F612
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Units — Seconds