Direct Access Parameter Information
W7B ASD Installation & Operation Manual
146
https://www.toshiba.com/tic/
Short Circuit Detection Time at Start
Program
Protection
Short Circuit Detect Pulse
This parameter determines when the system will perform an Output
Short Circuit test.
Settings:
0 — Check at Every Run
1 — Check at Every Power Up
Direct Access Number —
F613
Parameter Type —
Selection List
Factory Default —
Check at Every
Run
Changeable During Run —
No
Short Circuit Pulse Run Duration
Program
Protection
Short Circuit Detect Pulse
This parameter sets the pulse width of the ASD output pulse that is
applied to the motor during an Output Short Circuit test.
Direct Access Number —
F614
Parameter Type —
Numerical
Factory Default —
50
Changeable During Run —
No
Minimum — 1
Maximum — 100
Units — μS
Over-Torque Trip Selection
Program
Protection
Over-Torque Parameters
This parameter Enables/Disables the Over-Torque Tripping function.
When enabled, the ASD trips if an output torque value greater than the
setting of
or
exists for a time longer than the setting of
When disabled, the ASD does not trip due to over-torque conditions.
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number —
F615
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Over-Torque Detection Level During Power Running
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint
for over-torque tripping. This setting is a percentage of the maximum
rated torque of the drive.
Direct Access Number —
F616
Parameter Type —
Numerical
Factory Default —
150.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Over-Torque Detection Level During Regenerative Braking
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint
for over-torque tripping during regeneration. This setting is a percentage
of the maximum rated torque of the drive.
Direct Access Number —
F617
Parameter Type —
Numerical
Factory Default —
150.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %