Direct Access Parameter Information
W7B ASD Installation & Operation Manual
156
https://www.toshiba.com/tic/
Prohibit Initializing User Parameters During Typeform Initialization
Program
EOI Options
Preferences
This parameter Enables/Disables the ability to initialize user parameters
during a Type Form initialization.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number —
F709
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
V/f Group
No path available (Direct Access Only)
While operating using the CN8 Option 1 of 4 V/f groups may be selected
and run. Each V/f group is comprised of 4 user-defined variables: Base
Frequency, Base Frequency Voltage, Manual Torque Boost, and Motor
Overload Protection Level. Expanded descriptions of these parameters
may be found in this section (
Direct Access Parameter Information
).
Settings:
1 — Group 1
2 — Group 2
3 — Group 3
4 — Group 4
Note:
Press ESC from the Frequency Command screen to
access this parameter.
Note:
For additional information on this parameter, see
.
Direct Access Number —
F720
Parameter Type —
Selection List
Factory Default —
1
Changeable During Run —
Yes
Stop Pattern
No path available (Direct Access Only)
While operating using the CN8 Option the Stop Pattern parameter
determines the method used to stop the motor when the stop command
is issued via a Stop command from the LED Keypad.
The Decel Stop setting enables the Dynamic Braking system that is
setup at
or the DC Injection Braking system that is setup at
, and
.
The Coast Stop setting allows the motor to stop at the rate allowed by
the inertia of the load.
Settings:
1 — Decel Stop
2 — Coast Stop
Note:
The Stop Pattern setting has no effect on the Emergency Off
. If using the LCD EOI, press ESC from the Frequency
Command screen to access this parameter.
Direct Access Number —
F721
Parameter Type —
Selection List
Factory Default —
Decel Stop
Changeable During Run —
Yes