Direct Access Parameter Information
W7B ASD Installation & Operation Manual
158
https://www.toshiba.com/tic/
Low Output Disable Start Level
Program
Special
Low Output Disable Function
The Low Output Disable Start Level sets the output frequency threshold
that, if exceeded, will initiate the LOD function if properly configured.
Direct Access Number —
F732
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Max. Freq.
(
Units — Hz
Low Output Disable Start Time
Program
Special
Low Output Disable Function
The Low Output Disable Start Time sets the amount of time that the
LOD Start Level criteria must be met and maintained for the LOD
function to be initiated.
Direct Access Number —
F733
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Setpoint Boost
Program
Special
Low Output Disable Function
The Low Output Disable feature adds the user-input frequency value to
the commanded frequency.
Direct Access Number —
F734
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Max. Freq.
(
Units — Hz
Low Output Disable Boost Time
Program
Special
Low Output Disable Function
The Low Output Disable Boost Time sets the on-time timer for the LOD
Boost function.
Once expired, the LOD Boost function ceases.
Direct Access Number —
F735
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Feedback Level (Hz)
Program
Special
Low Output Disable Function
The Low Output Disable Feedback Level sets a frequency level that,
until the output of the ASD drops below this setting, the Restart Delay
Timer does not start.
Direct Access Number —
F736
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Max. Freq.
(
Units — Hz