Direct Access Parameter Information
W7B ASD Installation & Operation Manual
164
https://www.toshiba.com/tic/
Send Waiting Time (RS232/RS485) [0.00 = normal]
Program
Communications
Communication Settings
This parameter sets the RS232/RS485 response delay time.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Direct Access Number —
F825
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
ASD to ASD Communication (RS232/RS485)
Program
Communications
Communication Settings
In a master/follower configuration, this setting determines the output
parameter of the master ASD that will be used to control the applicable
follower ASDs.
Note:
Select No Follower if
is configured as a Master Output
controller. Otherwise, an EOI failure will result.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Settings:
0 — Normal (no follower)
1 — Frequency Reference
2 — Output Command Frequency
3 — Torque Command
4 — Output Torque Command
Direct Access Number —
F826
Parameter Type —
Selection List
Factory Default —
Normal
(no
follower)
Changeable During Run —
Yes
Command Request Disposition on Error
Program
Communications
Communication Error
In the event of a communication error during a transmission, the
command that was transmitted may be cleared or held.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Settings:
0 — Command Request Cleared
1 — Command Request Held
Direct Access Number —
F830
Parameter Type —
Selection List
Factory Default —
Command
Request Cleared
Changeable During Run —
Yes
Input Reference 1
Direct Access Number —
F831
Program
Communications
Scan Receive Settings
Parameter Type —
Numerical
Not used.
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 16
Summary of Contents for W7 DN-57442-006
Page 1: ...ADJUSTABLE SPEED DRIVES W7 DN 57442 006 INSTALLATION OPERATION MANUAL June 2020 ...
Page 2: ......
Page 3: ...Document Number 57442 006 Date June 2020 W7 ASD Installation and Operation Manual ...
Page 4: ......
Page 60: ......
Page 221: ......