Direct Access Parameter Information
W7B ASD Installation & Operation Manual
58
https://www.toshiba.com/tic/
Preset Speed 1
Program
Pattern Run
Preset Speeds
Up to 15 output frequency values that fall within the Lower-Limit and the
Upper-Limit range may be programmed into the drive and output as a
Preset Speed. This parameter assigns an output frequency to binary
number 0001 and is identified as Preset Speed 1. The binary number is
applied to S1 – S4 of the Control Terminal Strip to output the Preset
Speed.
Perform the following setup to allow the system to receive Preset Speed
control input at the S1 – S4 terminals:
1.
Program
Fundamental
Standard Mode Selection
Command
Mode Selection (0=Terminal Board).
2.
Program
Terminal
Input Terminals
S1 (set to Preset Speed
Bit 1; LSB of 4-bit count). Repeat for S2 – S4 (MSB of 4-bit count) as
Preset Speed Bit(s) 2 – 4, respectively (all Normally Open).
Note:
The default setting of S4 is EOff, but this terminal may be
re-assigned as the MSB.
3.
Program
Preset Speeds
1 (press Enter twice and set an output
frequency as Preset Speed 1; repeat for Preset Speeds 2 – 15 as
required).
4.
Program
Frequency
Preset Speed Operation Mode
Enabled.
When Enabled, the direction, accel/decel, and torque settings of
the Preset Speed being run are used.
When Disabled, only the speed setting of the Preset Speed being
run is used.
5.
Place the system in the Auto mode.
6.
Provide a Run command (connect F and/or R to CC).
Connect S1 to CC to run Preset Speed 1 (S1 to CC = 0001 binary).
With S1 – S4 configured to output Preset Speeds (
), 0001 –
1111 may be applied to S1 – S4 of the Terminal Board to run the
associated Preset Speed. If bidirectional operation is required, F and R
must be connected to CC, and Use Speed Modes must be enabled at
With S1 being the least significant bit of a binary count, the S1 – S4
settings will produce the programmed speed settings as indicated in the
Preset Speed Truth Table.
Direct Access Number —
F018
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — Lower-Limit
(
Maximum — Upper-Limit
(
Units — Hz
Preset Speed 2
Program
Pattern Run
Preset Speeds
This parameter assigns an output frequency to binary number 0010 and
is identified as Preset Speed 2. The binary number is applied to S1 – S4
of the Control Terminal Strip to output the Preset Speed (see
for
additional information on this parameter).
Direct Access Number —
F019
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — Lower-Limit
(
Maximum — Upper-Limit
(
Units — Hz
Preset Speed Truth Table.
Preset
S4
MSB
S3
S2
S1
LSB
Output
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
5
0
1
0
1
6
0
1
1
0
7
0
1
1
1
8
1
0
0
0
9
1
0
0
1
10
1
0
1
0
11
1
0
1
1
12
1
1
0
0
13
1
1
0
1
14
1
1
1
0
15
1
1
1
1
Note: 1 = Terminal connected to CC.