Direct Access Parameter Information
W7B ASD Installation & Operation Manual
60
https://www.toshiba.com/tic/
Low Speed Signal Output Frequency
Program
Terminal
Reach Settings
The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal so long as the ASD
output is at or above this setting (see
for the available
output assignments).
Direct Access Number —
F100
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Upper Limit
(
)
Units — Hz
Speed Reach Frequency
Program
Terminal
Reach Settings
The Speed Reach Frequency sets a frequency threshold that, when
reached or is within the bandwidth specified by parameter
, will
provide a signal at an output terminal that can close an appropriately
configured output contact (see
for the available output
assignments).
Direct Access Number —
F101
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Upper Limit
(
)
Units — Hz
Speed Reach Detection Band
Program
Terminal
Reach Settings
This parameter sets the bandwidth of the Speed Reach Frequency
(
setting.
Direct Access Number —
F102
Parameter Type —
Numerical
Factory Default —
2.5
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Upper Limit
(
)
Units — Hz