Direct Access Parameter Information
W7B ASD Installation & Operation Manual
62
https://www.toshiba.com/tic/
Forward/Reverse Run Priority When Both are Closed
Program
Terminal
Input Special Functions
The R/F Priority Selection determines the operation of the ASD if both
the R and F control terminals are activated.
Settings:
0 — Reverse
1 — Suspend
The waveforms depict the motor response for all combinations of the F
and R terminal settings if the Reverse option is chosen.
The Suspend setting will decelerate the motor to a stop regardless of the
rotation direction when both the F and R control terminals are activated.
Direct Access Number —
F105
Parameter Type —
Selection List
Factory Default —
Reverse
Changeable During Run —
No
Input Terminal Priority Selection
Program
Terminal
Input Special Functions
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Control Terminal Strip
even though the system is in the Hand mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Control Terminal Strip will receive priority
over commands from the EOI.
See
for additional information on using the Jog function.
See
for additional information on DC Injection Braking.
Settings:
0 — Disabled
1 — Enabled (Box checked)
Direct Access Number —
F106
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No