Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
63
16-Bit Binary/BCD Input Selection
Program
Terminal
Input Special Functions
The Extended Terminal Function is used with the optional ASD-Multicom
card only. This parameter defines the format of the binary or BCD data
when using the option card.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Inverted 12-Bit Binary
6 — Inverted 16-Bit Binary
7 — Inverted 3-Digit BCD
8 — Inverted 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the
configuration of terminals S1-S4 on the Control Terminal Strip as binary
bits 0 – 3 (
). The Frequency Mode 1 Selection
must
be set to Use Binary/BCD Input.
For proper scaling of the binary or BCD input, parameters
must be configured [BIN Reference Point 1, BIN Reference 1
(frequency), BIN Reference Point 2, and BIN Reference 2 (frequency
)
].
Direct Access Number —
F107
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
No
UP/DOWN Frequency Disposition at Power Down
Program
Frequency
Motorized Pot Settings
When the Frequency Mode 1 Selection
(
)
setting is set to Use MOP
Function Simulation, this parameter determines the outcome of the
Frequency Mode 1 setting at power down or stop.
Settings:
0 — Erase
1 — Store
If Erase is selected, then a set of 0.0 Hz is established when restarted
and the ASD will NOT store the frequency setpoint.
If Store is selected, the ASD will maintain the current frequency setpoint
in memory while stopped, during fault conditions, or when power is
removed. This setpoint will be used as the initial frequency setpoint
when the ASD is restarted.
A control terminal configured as MOP Frequency Clear will establish a
frequency setpoint of 0.0 Hz regardless of the UP/DOWN Frequency at
Power Down setting.
Direct Access Number —
F108
Parameter Type —
Selection List
Factory Default —
Erase
Changeable During Run —
No