Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
71
Input Terminal 3 (ST) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the ST
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact bounce or
chatter.
Direct Access Number —
F142
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 4 (RES) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the
RES terminal input by the programmed value (see waveforms at
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact bounce or
chatter.
Direct Access Number —
F143
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 5-8 (S1-S4) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the S1
– S4 terminal input by the programmed value (see waveforms at
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact bounce or
chatter.
Direct Access Number —
F144
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 9-16 (S5-S12) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the drive to any change in the S5
– S16 terminal input by the programmed value (see waveforms at
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact bounce or
chatter.
Direct Access Number —
F145
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS