Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
79
V/f Adjustment Coefficient
Program
Special
Special Parameters
This parameter may be used in the Constant Torque or the Variable
Torque modes only and should be adjusted gradually to improve the
application-specific torque requirements. The Torque Boost setting
(
) may be adjusted to improve the low-frequency torque
performance.
Note:
The Torque Boost setting should be adjusted gradually before
attempting performance corrections using this parameter.
Direct Access Number —
F183
Parameter Type —
Numerical
Factory Default —
32
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
V/f Five-Point 1 Frequency
Program
Special
V/f Five-Point Setting
The V/f Five-Point 1 Frequency setting establishes the frequency that is
to be associated with the voltage setting of
(V/f Five-Point 1
Voltage).
The V/f Five-Point settings define a custom volts per hertz relationship
for the startup output of the ASD.
To enable this function, set the V/f Pattern
(
selection to Custom V/f
Curve.
V/f Curves may be useful in starting high inertia loads such as rotary
drum vacuum filters.
Direct Access Number —
F190
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0
Maximum — 299
Units — Hz
V/f Five-Point 1 Voltage
Program
Special
V/f Five-Point Setting
The V/f Five-Point 1 Voltage establishes the percentage of the output
voltage that is to be associated with the frequency setting of
(V/f
Five-Point 1 Frequency).
See
for additional information on custom V/f curves.
Direct Access Number —
F191
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — 100.00
Units — %