Direct Access Parameter Information
W7B ASD Installation & Operation Manual
80
https://www.toshiba.com/tic/
V/f Five-Point 2 Frequency
Program
Special
V/f Five-Point Setting
The V/f Five-Point 2 Frequency sets the frequency to be associated with
parameter
(V/f Five-Point 2 Voltage).
See
for additional information on custom V/f curves.
Direct Access Number —
F192
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
No
Minimum — 0
Maximum — 299
Units — Hz
V/f Five-Point 2 Voltage
Program
Special
V/f Five-Point Setting
The V/f Five-Point 2 Voltage establishes the percentage of the output
voltage that is to be associated with the frequency setting of
(V/f
Five-Point 2 Frequency).
See
for additional information on custom V/f curves.
Direct Access Number —
F193
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
V/f Five-Point 3 Frequency
Program
Special
V/f Five-Point Setting
The V/f Five-Point 3 Frequency sets the frequency to be associated with
parameter
(V/f Five-Point 3 Voltage).
See
for additional information on custom V/f curves.
Direct Access Number —
F194
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz
V/f Five-Point 3 Voltage
Program
Special
V/f Five-Point Setting
The V/f Five-Point 3 Voltage establishes the percentage of the output
voltage that is to be associated with the frequency setting of
(V/f
Five-Point 3 Frequency).
See
for additional information on custom V/f curves.
Direct Access Number —
F195
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
V/f Five-Point 4 Frequency
Program
Special
V/f Five-Point Setting
The V/f Five-Point 4 Frequency sets the frequency to be associated with
parameter
(V/f Five-Point 4 Voltage).
See
for additional information on custom V/f curves.
Direct Access Number —
F196
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
No
Minimum — 0
Maximum — 299
Units — Hz
V/f Five-Point 4 Voltage
Program
Special
V/f Five-Point Setting
The V/f Five-Point 4 Voltage establishes the percentage of the output
voltage that is to be associated with the frequency setting of
(V/f
Five-Point 4 Frequency).
See
for additional information on custom V/f curves.
Direct Access Number —
F197
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %