Direct Access Parameter Information
W7B ASD Installation & Operation Manual
88
https://www.toshiba.com/tic/
RR Reference Point 2
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal
when this terminal is used as the control input while operating in the
Speed Control or the Torque Control mode.
See
for additional information on this setting.
This parameter sets the RR input level that represents RR Reference
Setpoint 2 (torque or frequency). This value is entered as 0 – 100% of
the 0 – 10 VDC RR input signal range.
Direct Access Number —
F212
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Units — %
RR Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal
when this terminal is used as the control input while operating in the
Speed Control mode.
See
for additional information on this setting.
This parameter sets RR Speed Frequency Setpoint 2 and is the
frequency that is associated with the setting of
.
Direct Access Number —
F213
Parameter Type —
Numerical
Factory Default —
80.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Units — Hz
RR Input Point 1 Torque
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the RR input terminal
when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for
a given RR input level and motor load.
See
for additional information on this setting.
This parameter sets RR Torque Reference Setpoint 1 and is the output
torque value that is associated with setting of
. This value is entered
as 0 – 250% of the rated torque.
Direct Access Number —
F214
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 250.0
Units — %
RR Input Point 2 Torque
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the RR input terminal
when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for
a given RR input level and motor load.
See
for additional information on this setting.
This parameter sets RR Torque Reference Setpoint 2 and is the output
torque value that is associated with setting of
. This value is entered
as 0 – 250% of the rated torque.
Direct Access Number —
F215
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 250.0
Units — %