This parameter is used to set the direction, gain, and bias of the RX2
input terminal when this terminal is used as the control input while
operating in the Speed Control mode.
See
for additional information on this setting.
This parameter sets RX2 Speed Frequency Setpoint 1 and is the
frequency that is associated with the setting of
Direct Access Number —
F223
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -Max. Freq.
)
Maximum — +Max. Freq.
Units — Hz
RX2 Reference Point 2
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the RX2
input terminal when this terminal is used as the control input while
operating in the Speed Control or the Torque Control mode.
See
for additional information on this setting.
This parameter sets the RX2 input level that represents RX2 Frequency
Setpoint 2 (direction/torque/frequency). This value is entered as
-100 to +100% of the -10 to +10 VDC RX2 input signal range.
Direct Access Number —
F224
Parameter Type —
Numerical
Factory Default — +
100.0
Changeable During Run —
Yes
Minimum — -100.0
Maximum — +100.0
Units — %
RX2 Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the RX2
input terminal when this terminal is used as the control input while
operating in the Speed Control mode.
See
for additional information on this setting.
This parameter sets RX2 Speed Frequency Setpoint 2 and is the
frequency that is associated with the setting of
Direct Access Number —
F225
Parameter Type —
Numerical
Factory Default — +
80.0
Changeable During Run —
Yes
Minimum — -Max. Freq.
)
Maximum — +Max. Freq.
Units — Hz
RX2 Input Point 1 Torque
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the RX2
input terminal when this terminal is used as the control input while
operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for
a given RX2 input level and motor load.
See
for additional information on this setting.
This parameter sets RX2 Torque Reference Setpoint 1 and is the output
torque value that is associated with the setting of
. This value is
entered as -250 to +250% of the rated torque.
Direct Access Number —
F226
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -250.0
Maximum — +250.0
Units — %