Direct Access Parameter Information
W7B ASD Installation & Operation Manual
https://www.toshiba.com/tic/
95
BIN Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the BIN
binary input terminals when these terminals are used as the control input
while operating in the Speed Control mode.
See
for additional information on this setting.
This parameter sets BIN Speed Reference Setpoint 1 (frequency) and is
the frequency that is associated with the setting of
.
Direct Access Number —
F229
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
BIN Reference Point 2
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the BIN
binary input terminals when these terminals are used as the control input
while operating in the Speed Control or the Torque Control mode.
See
for additional information on this setting.
This parameter sets BIN Reference Setpoint 2 (direction/torque/
frequency) and is entered as 0 to 100% of the BIN binary input word
11111111 (255D).
Direct Access Number —
F230
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Units — %
BIN Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the BIN
binary input terminals when these terminals are used as the control input
while operating in the Speed Control mode.
See
for additional information on this setting.
This parameter sets BIN Speed Reference Setpoint 2 (frequency) and is
the frequency that is associated with the setting of
.
Direct Access Number —
F231
Parameter Type —
Numerical
Factory Default — +
80.0
Changeable During Run —
Yes
Minimum — -Max. Freq.
)
Maximum — +Max. Freq.
Units — Hz
BIN Input Point 1 Torque
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the BIN
binary input terminals when these terminals are used as the control input
while operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for
a given BIN binary input and motor load.
See
for additional information on this setting.
This parameter sets BIN Torque Reference Setpoint 1 and is entered as
-250 to +250% of the rated torque.
Direct Access Number —
F232
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -250.0
Maximum — +250.0
Units — %